2006-10-17 10:12:42 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} THE RISER DIAGRAM LOCATES PANEL "C" IN THE GARAGE,
 SHEET E-1 LOCATES A "NEW " PANELBOARD"C" IN THE
 LAUNDRY. THERE IS NO SUB FEED TO THIS "NEW" PANEL ON
 THE RISER. PLEASE CLARIFY.
  
 3} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. THEY WEREON
 THE PERMIT SET, BUT OMMITED FROM THE REVISED SET.
  
 4} THE CABANA NOW BEING REMOVED PER SHEET SP-1, PANEL
 "CB-B" NOTE TO CABANA WOULD BE INCORRECT.. SUBMIT A
 SCHEDULE FOR "CB-CB" IF TO BE USED.
  
 NOTE: THE GENERATOR SHOWN ON THE REVISION MUSTBE
 PERMITTED SEPARATELY AS A GEN-RES PERMIT TYPE, WITH ALL
 REQUIRED DOCUMENTS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.