Plan Review Notes
Plan Review Notes For Permit 05051311
Permit Number 05051311
Review Stop M
Sequence Number 3
Notes
Date Text
2006-10-17 13:53:28REVISION TO MECHANICAL PLAN PAGE M-2.
 *** DENIED ***
 1) PLEASE ALSO SUBMIT PAGE M-1 AS THIS PAGE NEVER
 PASSED A MECHANICAL REVIEW.
  
 2) IT WOULD BE ADVISABLE TO REVISE YOUR ENERGY
 CALCULATIONS ALSO AS THE ONE ON FILE IS CALLING FOR
 15.50 SEER A/C SYSTEMS AND YOUR PLANS PAGE M-2SYSTEM
 #2 IS ONLY 15.00 SEER.
  
 3) ALSO YOU SHOULD REVISE YOUR MANUAL J CALCULATION AS
 THE PLANS ARE CALLING FOR MORE SENSIBLE BTU'S THAN THE
 MANUAL J CAL' S ON FILE WILL PERMIT.
  
 4) SEE PAGE M-2 MASTER BEDROOM, NEED TO PROVIDE RETURN
 AIR, PER 2001 FBC/M 601.4 .
  
 5) SEE PAGE M-2 AHU #4, RETURN AIR GRILL IS NOT SIZED,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  