Plan Review Notes For Permit 05051311 |
Permit Number |
05051311 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-10-17 13:53:28 | REVISION TO MECHANICAL PLAN PAGE M-2. | | *** DENIED *** | | 1) PLEASE ALSO SUBMIT PAGE M-1 AS THIS PAGE NEVER | | PASSED A MECHANICAL REVIEW. | | | | 2) IT WOULD BE ADVISABLE TO REVISE YOUR ENERGY | | CALCULATIONS ALSO AS THE ONE ON FILE IS CALLING FOR | | 15.50 SEER A/C SYSTEMS AND YOUR PLANS PAGE M-2SYSTEM | | #2 IS ONLY 15.00 SEER. | | | | 3) ALSO YOU SHOULD REVISE YOUR MANUAL J CALCULATION AS | | THE PLANS ARE CALLING FOR MORE SENSIBLE BTU'S THAN THE | | MANUAL J CAL' S ON FILE WILL PERMIT. | | | | 4) SEE PAGE M-2 MASTER BEDROOM, NEED TO PROVIDE RETURN | | AIR, PER 2001 FBC/M 601.4 . | | | | 5) SEE PAGE M-2 AHU #4, RETURN AIR GRILL IS NOT SIZED, | | PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|