Date Text
2005-12-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}SEE ATTACHED FOR GENERATOR SUBMITTAL
 REQUIREMENTS.
  
 2} THE 400 AMP DISCONNECT ON THE RISER
 IS LABELED "DOUBLE THROW", PLEASE SEE
 230.70, THE DISCONNECTING MEANS MUST
 HAVE AN CENTER OFF OR SOME MEANS OF
 DISCONNECTING ALL CONDUCTORS. ALSO SEE
 IT MUST BE SERVICE RATED PER
 230.70(C).IS THIS A MANUAL DISCONNECT?
  
 3} PLEASE SEE THAT THE DISHWASHER,
 DISPOSAL LISTEDIN THE LOAD CALCS ARE NOT
 ON THE PANEL SCHEDULE.
  
 4} THE PACKAGED SEWER SYSTEM IS NOT ON
 THE SCHEDULE OR CALCS.
  
 PLEASE INCREASE THE VALUE TO INCLUDE THE
 GENERATOR WITH ALL LABOR AND MATERIAL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  