2005-12-23 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1}SEE ATTACHED FOR GENERATOR SUBMITTAL | | REQUIREMENTS. | | | | 2} THE 400 AMP DISCONNECT ON THE RISER | | IS LABELED "DOUBLE THROW", PLEASE SEE | | 230.70, THE DISCONNECTING MEANS MUST | | HAVE AN CENTER OFF OR SOME MEANS OF | | DISCONNECTING ALL CONDUCTORS. ALSO SEE | | IT MUST BE SERVICE RATED PER | | 230.70(C).IS THIS A MANUAL DISCONNECT? | | | | 3} PLEASE SEE THAT THE DISHWASHER, | | DISPOSAL LISTEDIN THE LOAD CALCS ARE NOT | | ON THE PANEL SCHEDULE. | | | | 4} THE PACKAGED SEWER SYSTEM IS NOT ON | | THE SCHEDULE OR CALCS. | | | | PLEASE INCREASE THE VALUE TO INCLUDE THE | | GENERATOR WITH ALL LABOR AND MATERIAL. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|