Plan Review Notes
Plan Review Notes For Permit 05051311
Permit Number 05051311
Review Stop P
Sequence Number 2
Notes
Date Text
2005-12-28 00:00:00DENIED;
 1.L.P. GAS PLANS TO BE SUBMITED BY
 LICENSED L.P. CONTRACTOR, AT TIME OF
 APPLICATION. SHOW SIZE AND LOCATION OF
 TANK, DEVELOPED LENGHT AND PIPE DIAMETER
 ALSO TYPE AND LOCATION OF REGULATORS.
 2.A RESIDENTAL GENERATOR PERMIT IS
 REQUIRED FOR INSTALLATION OF A
 GENERATOR. ELECTRICAL CONTRACTOR MUST
 SUBMIT PLANS WITH PERMIT APPLICATION AND
 MUST BE REVIEW BY
 BUILDING,MECHANICAL,PLUMBING ZONING AND
 ELECTRICAL PLAN REVIEW.
 3.2ND REQUEST, PLUMBING PLAN REVIEW
 CANNOT BE DONE WITHOUT A SANITARY RISER
 DIAGRAM.
 4.SHOW RAIN WATER CALKULATIONS FOR
 GUTTERS AND DOWN SPOUTS AND EMERGENSE
 DRAINS AS REQUIRED BY FBC PLUMBING
 CHAPTER 11.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695