2005-06-21 00:00:00 | DENIED |
| |
| 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| 90 DAYS OF RECORDING. |
| |
| 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.PRODUCT APPROVALS REQUIRED FOR FLAT |
| ROOF STRAPS AND TIE-DOWNS, LINTELS AND |
| OVERHEAD DOOR. |
| **NOTE... ALL PRODUCT APPROVALS |
| SUBMITTED SHALL HAVE THE FOLLOWING STATE |
| APPROVAL ATTACHED.** |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 4. SHOW STAIR DETAILS COMPLYING WITH |
| FBC1007.8.3 |
| |
| 5.BUILDING IS IN AN AREA OF |
| QUESTIONABLE SOILS, FLOOD ZONE "A". |
| SUBMIT A SOILS REPORT CONTAINING |
| RECOMMENDATIONS FOR FOOTINGS AND |
| FOUNDATIONS. |
| |
| 6.PROJECT IMPROVEMENT IS CONSIDERED A |
| SUBSTANTIAL IMPROVEMENT SEC 94-611 WPB |
| DEFINITIONS. |
| SINCE EXISTING BUILDING IS IN A FLOOD |
| ZONE THE EXISTING STRUCTURE SHALL BE |
| BROUGHT UP TO 6 INCHES ABOVE THE BASE |
| ELEVATION OF 7 FEET. OR A FINISH FLOOR |
| HEIGHT OF 7FT. 6INCHES. |
| THE EXISTING STRUCTURE IS CURRENTLY AT |
| 5.58FT.. |
| NOTE: A/C PADS SHALL BE AT THE 7'6" |
| FINISH FLOOR HEIGHT. |
| |
| 7.SUBMIT AN APPROVED APPLICATION FOR |
| HOMESTEAD EXEMPTION OR HAVE A CONTRACTOR |
| PULL PERMITS FS 489 |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |