Plan Review Notes
Plan Review Notes For Permit 05051279
Permit Number 05051279
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-31 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT A RISER DIAGRAM INDICATING HOW
 THE 100 AMP PANELIS BEING FED, INCLUDE
 CONDUIT AND CONDUCTOR NUMBER AND SIZES.
  
 2} SHOW GROUNDING PER 250.32.
  
 3} ALL SHEETS DRAWN BY THE ARCHITECT
 MUST COMPLY WITH 481 FBC AND BE SEALED
 PER 61G1-16.003 FAC.
  
 4} INCREASE THE PERMIT VALUE TO INCLUDE
 ALL LABOR AND MATERIAL, ALSO DESIGN
 COSTS PER 104.6.5. GIVE THE UPDATED
 INFORMATION TO THE PERMIT CLERK ATB TIME
 OF RESUBMITTAL SO ADJUSTMENTS CAAN BE
 MADE IN THE FEES PRIOR TO REVIEWS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026