Plan Review Notes For Permit 05051279 |
Permit Number |
05051279 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-31 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SUBMIT A RISER DIAGRAM INDICATING HOW | | THE 100 AMP PANELIS BEING FED, INCLUDE | | CONDUIT AND CONDUCTOR NUMBER AND SIZES. | | | | 2} SHOW GROUNDING PER 250.32. | | | | 3} ALL SHEETS DRAWN BY THE ARCHITECT | | MUST COMPLY WITH 481 FBC AND BE SEALED | | PER 61G1-16.003 FAC. | | | | 4} INCREASE THE PERMIT VALUE TO INCLUDE | | ALL LABOR AND MATERIAL, ALSO DESIGN | | COSTS PER 104.6.5. GIVE THE UPDATED | | INFORMATION TO THE PERMIT CLERK ATB TIME | | OF RESUBMITTAL SO ADJUSTMENTS CAAN BE | | MADE IN THE FEES PRIOR TO REVIEWS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|