2005-06-26 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05051234 |
| ADD: 1665 PALM BEACH LAKES/ 700 |
| CONT: MJS CONSTR |
| TEL: (561)722-1276 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 3)412.6.2 OPENINGS IN THE ELEVATOR |
| LOBBY SHALL BE LIMITED TO THOSE |
| REQUIRED FOR ACCESS TO THE ELEVATORS AND |
| FOR EGRESS FROM THE BUILDING. |
| ALL ROOMS AND ENCLOSURES SHALL HAVE AT |
| LEAST ONE REQUIRED EXIT ACCESSIBLE |
| WITHOUT TRAVEL THROUGH THE ELEVATOR |
| LOBBY.OPENINGS MAY BE PROVIDED WITH |
| HORIZONTAL SLIDING DOORS CONFORMING TO |
| |
| 4)1012.4.EXIT STAIRWAYS, CHUTES, |
| JANITOR CLOSETS, GUEST ROOMS, SERVICE |
| ROOMS, ETC., SHALL NOT OPEN INTO THE |
| ELEVATOR LOBBY. |
| |
| 5)412.6.3 EACH ELEVATOR LOBBY SHALL BE |
| PROVIDED WITH AN APPROVED SMOKE |
| DETECTOR LOCATED ON THE LOBBY CEILING. |
| WHEN THE DETECTOR IS ACTIVATED, |
| ELEVATOR DOORS SHALL NOT OPEN AND ALL |
| CARS SERVING THAT LOBBY ARE TO RETURN TO |
| THE MAIN FLOOR AND BE UNDER MANUAL |
| CONTROL ONLY.IF THE MAIN FLOOR |
| DETECTOR OR A TRANSFER FLOOR DETECTOR IS |
| ACTIVATED, ALL CARS SERVING THE MAIN |
| FLOOR OR TRANSFER FLOOR SHALL RETURN TO |
| A LOCATION APPROVED BY THE FIRE |
| DEPARTMENT AND BUILDING OFFICIAL AND BE |
| UNDER MANUAL CONTROL ONLY.THE DETECTOR |
| MAY SERVE TO CLOSE THE LOBBY DOORS. |
| |
| 5) DOOR INTO OFFICE 725 DOESN'T MEET: |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| 11-4.1.6(2) DUTY TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| AREAS SHALL BE DEEMED DISPROPORTIONATE |
| TO THE OVERALL ALTERATION WHEN THE COST |
| EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| TION TO THE PRIMARY FUNCTION AREA. |
| (A)(I) AN ACCESSIBLE ENTRANCE |
| (II) AN ACCESSIBLE ROUTE |
| (III) AT LEAST ONE ACCESSIBLE REST- |
| ROOM FOR EACH SEX OR A SINGLE |
| UNISEX RESTROOM |
| (IIII) ACCESSIBLE TELEPHONE |
| (IV) ELEMENTS SUCH AS PARKING, STOR- |
| AGE OR ALARMS. |
| |
| 6) UPDATE OR CHANGE SCOPE OF WORK ON THE |
| PERMIT APPLICATION TO REFLECT WORK ON |
| THE WHOLEOF THE 7TH FLOOR NOT JUST |
| SIUTE 700.IF WORK IS TO BE COMPLETED |
| UNDER THIS PERMIT IS ONLY SUITE 700 ALL |
| OTHER WORK AREAS WILL BE STRUCK OFF THE |
| PLANS. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |