Plan Review Notes
Plan Review Notes For Permit 05051108
Permit Number 05051108
Review Stop E
Sequence Number 6
Notes
Date Text
2007-03-29 20:53:37 
  
 ****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE SEE THE PLANS SUBMITTED ARE NOW MORE COMPLETE
 PLANS FOR REVIEW FOR CODE COMPLIANCE. PLEASE SEE THERE
 ARE NEW COMMENTS BASED ON THE PLANS SUBMITTED.
 THE PREVIOUS REVIEW REQUESTED PLANS TO BE COMPLETED FOR
 CODE COMPLIANCE.
  
 1) NOTE: PLEASE SEE ALL CIRCUITING HAS NOW BEEN REMOVED
 FROM PLANS. PLEASE SEE BY DOING SO SOME ITEMS DO NOT
 INDICATE HOW THEY ARE BEING CONTROLLED.
 PLEASE SEE OUTSIDE FLOODS?
 HOW ARE THESE CONTROLLED?
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PANEL SCHEDULE IS NOT SHOWING ANY
 WIRE SIZES TO BE REVIEWED FOR CODE COMPLIANCE. 240.4,
 310.16, 408.4
 FBC 106.3.5.4.
  
 3) NOTE: PLEASE CLARIFY THE SMOKE DEVICES AS SOME WHICH
 ARE BEING SHOWN AS SD ARE NOTED AS SMOKE DETECTORS AND
 SOME WITH THE S SYMBOLS ARE ALSO NOTED AS SMOKE
 DETECTORS?
 PLEASE SEE NFPA-72 DEFINITIONS FOR TYPES OF DEVICES. IF
 SMOKE ALARMS, INDICATE AS SA.
 PLEASE SEE THE PANEL SCHEDULE SHOWS THE 120VA HARDWIRED
 DEVICES AS SMOKE DETECTORS, WHICH IS NOT POSSIBLE.
 PLEASE SEE NOTE ON PANEL SCHEDULE WHICH ALSO MENTIONS
 SMOKE DETECTORS??
 IF THERE ARE MULTIPLE TYPES OF DEVICES INSTALLED,
 PLEASE CLARIFY AND ALSO INDICATE IF TIED INTO A FA OR
 SECURITY SYSTEM W/ SOUNDING DEVICES. IF SD IS USED,
 THEN SOUNDING DEVICES ARE REQUIRED TO ALERT AN OCCUPANT
 IN THE EVENT OF ALARM STATUS.
 NFPA-72 2002 11.5.1.1.1, 11.8.3
  
 4) NOTE: PLEASE CORRELATE THE RISER WITH THE PANELS.
 PLEASE SEE PANEL *A* IS BEING SHOWN AS A 400A RATED
 PANEL WITH A 350AMP MAIN WHEN THE PANEL ON RISER IS
 SHOWN AS 200AMPS??
 PLEASE KNOW THAT DEPENDING ON WHICH IS ACTUALLY
 INSTALLED; THE RISER MAY NEED TO BE COMPLETELY REVISED
 TO INCREASE SERVICE, CONDUCTORS GROUNDING ETC. 215.5,
 310.16, 240.4 ETC.
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE 310.15B6, 250.66 AS THE SERVICE IS
 BEING SHOWN AS 400AMPS, OR MORE DEPENDING ON NOTE #4
 ABOVE. MINIMUM SIZE GEC IS 1/0.
  
 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS, OR SMOKE
 DETECTORS IN BEDROOMS ON 2ND FLOOR. BED-RM #4, AND
 OFFICE WHICH IS CONSIDERED AN ADAPTABLE SLEEPING ROOM.
 NFPA-72 11.5.1.1.1
  
 7) NOTE: PLEASE SEE THE VALUE FOR THE LOW VOLTAGE
 PERMIT AS PREVIOUSLY NOTED AHS NOT BEEN INCREASED BY
 THE CONTRACTOR. PLEASE KNOW THAT A VALUE WILL BE
 ASSESSED BY THIS OFFICE USING THE MARSHALL'S AND SWIFT
 GUIDE WHICH IS ADOPTED INTO THE FBC PER 108.3
  
 8) NOTE: PLEASE SEE 220.3B4 AS THE RECESSED LIGHTING AS
 REDLINED ON NOTES ON PREVIOUS PLANS NEEDS TO BE SHOWN
 IN LOAD CALCULATIONS.
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTERSPACES ARE TO BE SHOWN AS GFI OR GFI
 PROTECTED.
  
 ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME
 INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF
 SUBMITTED PLANS COULD BE DONE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]