Plan Review Notes
Plan Review Notes For Permit 05051108
Permit Number 05051108
Review Stop E
Sequence Number 5
Notes
Date Text
2007-03-08 15:45:33** UNSAT **
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED ARE NOT
 COMPLETE AT THIS TIME FOR COMPLETE REVIEW OF CODE
 COMPLIANCE.
 PLEASE KNOW THAT THERE MAY BE COMMENTS ONCE PLANS ARE
 COMPLETE.
  
 2) NOTE: PLEASE SEE *PROVISO* WHICH WAS GIVEN IN
 SEPTEMBER OF 05 WHICH REQUIRED THOSE ITEMS TO BE
 REVISED *BEFORE ROUGH*. THIS WAS NOT DONE YET ROUGH
 ELECTRICAL INSPECTION WAS CALLED IN WITH NOTES ATTACHED
 TO PLANS.
 INSPECTOR INFORMED THIS OFFICE THAT THE NOTES WHICH
 WERE ATTACHED TO PLANS WERE TORN OFF.
 PLEASE COMPLETE THE FOLLOWING.
  
 PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH REVISED PANEL SCHEDULES TO BE REVISED AND
 SUBMITTED. PLEASE SEE MANY ITEMS ON PLANS DO NOT
 CONTAIN CIRCUITING AND REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE AT THIS TIME.
 PLEASE COMPLETE AND SUBMIT LOAD CALCULATIONS PER NEC.
 PLEASE CORRELATE LOADS ON PANEL SCHEDULES AND COMPLETE
 AS REQUIRED PER CODE AND PREVIOUS *PROVISO *NOTES.
 PLEASE SUBMIT THE COMPLETE ELECTRICAL RISER DIAGRAM TO
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE BE SURE TO SEE THE 2002 NEC.
 210.52,210.11, 220, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.4 ETC.
  
 3) NOTE: PLEASE SEE THE DEVICES WHICH ARE SHOWN AS
 SMOKE DETECTORS SHOULD BE SHOWN AS SMOKE ALARMS IF THEY
 ARE 120V WITH DETECTION AND SOUNDING IN THE SINGLE
 UNIT.
 PLEASE SEE NFPA-72 DEFINITIONS FOR THE DIFFERENCES FROM
 SMOKE DETECTORS AND SMOKE ALARMS.
  
 4) NOTE: PLEASE SEE THERE ARE NOW NUMEROUS LOW VOLTAGE
 ITEMS ON PLANS WHICH THE LOW VOLTAGE PERMIT WAS UNDER
 VALUED BASED ON PLANS.
 PLEASE HAVE THE CONTRACTOR INCREASE VALUE FOR ALL LV
 WORK AS SHOWN WHICH SHALL INCLUDE ALL LABOR AND
 MATERIALS EVEN IF OWNER SUPPLIED.
 PLEASE KNOW A VALUE MAY BE ACCESSED BY THIS OFFICE IF
 AN APPROPRIATE VALUE IS NOT APPLIED.**
 FBC 108.3
  
 ** PLEASE KNOW A HOLD IS NOW BEING PLACED ON THE
 ELECTRICAL AND BUILDING PERMIT ON INSPECTIONS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]