Date |
Text |
2007-03-08 15:45:33 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THE PLANS SUBMITTED ARE NOT |
| COMPLETE AT THIS TIME FOR COMPLETE REVIEW OF CODE |
| COMPLIANCE. |
| PLEASE KNOW THAT THERE MAY BE COMMENTS ONCE PLANS ARE |
| COMPLETE. |
| |
| 2) NOTE: PLEASE SEE *PROVISO* WHICH WAS GIVEN IN |
| SEPTEMBER OF 05 WHICH REQUIRED THOSE ITEMS TO BE |
| REVISED *BEFORE ROUGH*. THIS WAS NOT DONE YET ROUGH |
| ELECTRICAL INSPECTION WAS CALLED IN WITH NOTES ATTACHED |
| TO PLANS. |
| INSPECTOR INFORMED THIS OFFICE THAT THE NOTES WHICH |
| WERE ATTACHED TO PLANS WERE TORN OFF. |
| PLEASE COMPLETE THE FOLLOWING. |
| |
| PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE |
| WITH REVISED PANEL SCHEDULES TO BE REVISED AND |
| SUBMITTED. PLEASE SEE MANY ITEMS ON PLANS DO NOT |
| CONTAIN CIRCUITING AND REVIEW FOR CODE COMPLIANCE CAN |
| NOT BE DONE AT THIS TIME. |
| PLEASE COMPLETE AND SUBMIT LOAD CALCULATIONS PER NEC. |
| PLEASE CORRELATE LOADS ON PANEL SCHEDULES AND COMPLETE |
| AS REQUIRED PER CODE AND PREVIOUS *PROVISO *NOTES. |
| PLEASE SUBMIT THE COMPLETE ELECTRICAL RISER DIAGRAM TO |
| BE REVIEWED FOR CODE COMPLIANCE. |
| PLEASE BE SURE TO SEE THE 2002 NEC. |
| 210.52,210.11, 220, 310.16, 240.4 ETC |
| FBC 106.1.2, 106.3.5.4 ETC. |
| |
| 3) NOTE: PLEASE SEE THE DEVICES WHICH ARE SHOWN AS |
| SMOKE DETECTORS SHOULD BE SHOWN AS SMOKE ALARMS IF THEY |
| ARE 120V WITH DETECTION AND SOUNDING IN THE SINGLE |
| UNIT. |
| PLEASE SEE NFPA-72 DEFINITIONS FOR THE DIFFERENCES FROM |
| SMOKE DETECTORS AND SMOKE ALARMS. |
| |
| 4) NOTE: PLEASE SEE THERE ARE NOW NUMEROUS LOW VOLTAGE |
| ITEMS ON PLANS WHICH THE LOW VOLTAGE PERMIT WAS UNDER |
| VALUED BASED ON PLANS. |
| PLEASE HAVE THE CONTRACTOR INCREASE VALUE FOR ALL LV |
| WORK AS SHOWN WHICH SHALL INCLUDE ALL LABOR AND |
| MATERIALS EVEN IF OWNER SUPPLIED. |
| PLEASE KNOW A VALUE MAY BE ACCESSED BY THIS OFFICE IF |
| AN APPROPRIATE VALUE IS NOT APPLIED.** |
| FBC 108.3 |
| |
| ** PLEASE KNOW A HOLD IS NOW BEING PLACED ON THE |
| ELECTRICAL AND BUILDING PERMIT ON INSPECTIONS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |