2006-02-15 00:00:00 | ********** UNSAT ************* |
| |
| |
| 1)NOTE: PLEASE SEE "PROVISO" NOTES FROM |
| 9/29/05 WHICH HAVE NOT BEEN ADDRESSED OR |
| SUBMITTED. |
| PLEASE SEE THE PERMIT WAS ISSUED ON THE |
| CONDITION THESE ITMES BE ADDRESSED, CODE |
| COMPLIANT AND RETURNED FOR REVIEW. |
| PLEASE SEE NOTES BELOEW. |
| |
| 2)NOTE: PLEASE CORRELATE ALL PANELS, |
| LOADS ETC. |
| PLEASE SUBMIT LOADS CALCUALTIONS WHICH |
| MEET THE NEC 220 |
| PLEASE CORRELATE LOADS ON PANELS ETC. |
| PLEASE RE-FIGURE AS REQUESTED ON |
| PREVIOUS REVIEW. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE MANY ITEMS FOR |
| PREVIOUS "PROVISO" CAN BE REVIEWED FOR |
| CORRECTED ITEMS AS THE FIRST FLR PLANS |
| WERE NOT SUBMITTED.? |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE RISER HAS NOW BEEN |
| REVISED TO REMOVED GROUNDING ELECTODE |
| ATTACHMENT TO FOOTER STEEL, HOWEVER THIS |
| ATTACHMENT FOR NEW CONSTRUCTION IS |
| REQUIRED TO BE INSTALLED PER 250.50, |
| 250.52A |
| THIS SHALL NOT BE DELETED FROM PLANS AND |
| RISER. |
| |
| 5)NOTE: PLEASE SEE A NEW DETAIL WAS |
| SUBMITTED FOR A "HURRICANE ROOM" HOWEVER |
| PLANS WERE NOT REVISED TO SHOW THIS |
| ROOM, LTS, RECEPTS ETC. 210.52,210.70 |
| ETC. |
| PLEASE ALSO SEE BLDG COMMENTS AS THE |
| 8 1/2X 11 IS MISSING THE TITLE BLOCK FOR |
| ARCHITECT AND OTHER POSSIBLE INFORMATION |
| NEEDED FOR BLDG REVIEW. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| AND OTHER INFORMATION FOR REVIEW. |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |