Plan Review Notes
Plan Review Notes For Permit 05051108
Permit Number 05051108
Review Stop E
Sequence Number 4
Notes
Date Text
2006-02-15 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE SEE "PROVISO" NOTES FROM
 9/29/05 WHICH HAVE NOT BEEN ADDRESSED OR
 SUBMITTED.
 PLEASE SEE THE PERMIT WAS ISSUED ON THE
 CONDITION THESE ITMES BE ADDRESSED, CODE
 COMPLIANT AND RETURNED FOR REVIEW.
 PLEASE SEE NOTES BELOEW.
  
 2)NOTE: PLEASE CORRELATE ALL PANELS,
 LOADS ETC.
 PLEASE SUBMIT LOADS CALCUALTIONS WHICH
 MEET THE NEC 220
 PLEASE CORRELATE LOADS ON PANELS ETC.
 PLEASE RE-FIGURE AS REQUESTED ON
 PREVIOUS REVIEW.
 215.5
  
 3)NOTE: PLEASE SEE MANY ITEMS FOR
 PREVIOUS "PROVISO" CAN BE REVIEWED FOR
 CORRECTED ITEMS AS THE FIRST FLR PLANS
 WERE NOT SUBMITTED.?
 215.5
  
 4)NOTE: PLEASE SEE RISER HAS NOW BEEN
 REVISED TO REMOVED GROUNDING ELECTODE
 ATTACHMENT TO FOOTER STEEL, HOWEVER THIS
 ATTACHMENT FOR NEW CONSTRUCTION IS
 REQUIRED TO BE INSTALLED PER 250.50,
 250.52A
 THIS SHALL NOT BE DELETED FROM PLANS AND
 RISER.
  
 5)NOTE: PLEASE SEE A NEW DETAIL WAS
 SUBMITTED FOR A "HURRICANE ROOM" HOWEVER
 PLANS WERE NOT REVISED TO SHOW THIS
 ROOM, LTS, RECEPTS ETC. 210.52,210.70
 ETC.
 PLEASE ALSO SEE BLDG COMMENTS AS THE
 8 1/2X 11 IS MISSING THE TITLE BLOCK FOR
 ARCHITECT AND OTHER POSSIBLE INFORMATION
 NEEDED FOR BLDG REVIEW.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 AND OTHER INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]