2005-09-29 00:00:00 | ********** PROVISO/ REVISION ********** |
| |
| PLEASE SEE ITEMS BELOW ALONG WITH ANY |
| OTHER REVISIONS MUST BE SUBMITTED FOR |
| REVIEW AND STAMPING BEFORE ANY ROUGH |
| ELECTRICAL INSPECTION. |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: PLEASE SEE SMOKE DETECTORS ARE |
| REQUIRED ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING LEADING TO THE FLOOR ABOVE IN |
| THE IMEDIATE VICINITY OF STAIRS. |
| PLEASE SEE MISSING SD AT REAR FOYER |
| LOWER LEVEL. |
| PLEASE SEE SD AT FRONT FOYER REQUIRED ON |
| WALL NO MORE THAN 10' ABOVE FF. |
| |
| 2)NOTE: PLEASE SEE MIN CONTROL AND |
| EGRESS LIGHT FIXTURE(S) REQUIRED AT REAR |
| FOYER ENTRY/ EXIT. |
| PLEASE ALSO SEE MEANS OF EGRESS FROM |
| LAUNDRY RM AND BEDRM #3.3-WAY/4-WAY |
| SWITCHES REQUIRED. |
| PLEASE SEE SEE A "GAS FIXURE" MAY BE |
| INSTALLED ALSO, HOWEVER AN ELECTRICAL SW |
| AND FIXTURE IS REQUIRED. |
| PLEASE SEE FRONT PORCH IS OK, DUE TO |
| ELECTRICAL RECESSED LTS ALONG W/GAS FIX. |
| 210.70, LS 101 7.8 |
| |
| 3)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 |
| |
| 4)NOTE: PLEASE SEE "DEN" RECEPTS (A-32) |
| CIRCUITED TO SMALL APPL CIRCUIT. |
| BRKFST AREA, DINING AREA MAY NOT FEED |
| OTHER ARES. |
| PLEASE ADJUST. |
| |
| 5)NOTE: PLEASE CORRELATE ALL LOADS ON |
| PANELS AND LOAD CALCUALTIONS. |
| PLEASE GO THROUGH LOAD CALCULATIONS AND |
| RE-FIGURE TO MEET NEC 220. |
| PANEL "A" SHOWS 30KVA FOR PANEL "B", |
| HOWEVER PANEL "B" SHOWS 40KVA. |
| SEE PANEL "C" ETC. |
| |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE. |
| |