2005-09-29 00:00:00********** PROVISO/ REVISION **********
  
 PLEASE SEE ITEMS BELOW ALONG WITH ANY
 OTHER REVISIONS MUST BE SUBMITTED FOR
 REVIEW AND STAMPING BEFORE ANY ROUGH
 ELECTRICAL INSPECTION.
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE SMOKE DETECTORS ARE
 REQUIRED ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING LEADING TO THE FLOOR ABOVE IN
 THE IMEDIATE VICINITY OF STAIRS.
 PLEASE SEE MISSING SD AT REAR FOYER
 LOWER LEVEL.
 PLEASE SEE SD AT FRONT FOYER REQUIRED ON
 WALL NO MORE THAN 10' ABOVE FF.
  
 2)NOTE: PLEASE SEE MIN CONTROL AND
 EGRESS LIGHT FIXTURE(S) REQUIRED AT REAR
 FOYER ENTRY/ EXIT.
 PLEASE ALSO SEE MEANS OF EGRESS FROM
 LAUNDRY RM AND BEDRM #3.3-WAY/4-WAY
 SWITCHES REQUIRED.
 PLEASE SEE SEE A "GAS FIXURE" MAY BE
 INSTALLED ALSO, HOWEVER AN ELECTRICAL SW
 AND FIXTURE IS REQUIRED.
 PLEASE SEE FRONT PORCH IS OK, DUE TO
 ELECTRICAL RECESSED LTS ALONG W/GAS FIX.
 210.70, LS 101 7.8
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 4)NOTE: PLEASE SEE "DEN" RECEPTS (A-32)
 CIRCUITED TO SMALL APPL CIRCUIT.
 BRKFST AREA, DINING AREA MAY NOT FEED
 OTHER ARES.
 PLEASE ADJUST.
  
 5)NOTE: PLEASE CORRELATE ALL LOADS ON
 PANELS AND LOAD CALCUALTIONS.
 PLEASE GO THROUGH LOAD CALCULATIONS AND
 RE-FIGURE TO MEET NEC 220.
 PANEL "A" SHOWS 30KVA FOR PANEL "B",
 HOWEVER PANEL "B" SHOWS 40KVA.
 SEE PANEL "C" ETC.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  