Plan Review Notes For Permit 05051108 |
Permit Number |
05051108 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-07 00:00:00 | *** DENIED *** | | 1) PLEASE SHOW WHICH SUB-SECTION OF | | SECTION 703 FBC/M 2001 YOU ARE USING | | TO OBTAIN COMBUSTION AIR FOR THE | | LAUNDRY ROOM. | | 2) SUPPLY AIR DUCTS (MAIN TRUNK LINES & | | BRANCH LINES) ARE NOT PROPERLY SIZED | | FOR ADEQUATE AIR DISRIBUTION. | | 3) RETURN AIR DUCTS TO AHU'S ARE NOT | | PROPERLY SIZED PER 2001 FBC/M 601.4. | | 4) RETURN AIR GRILLS TO AHU'S ARE NOT | | SIZED (18"X18" WOULD BE TO SMALL). | | 5) SUPPLY AIR DUCTS CAN NOT GO TO | | CLOSETS IN GARAGE (HAZARDOUS FUMES | | MAY ENTER DUCTS WHEN UNIT IS NOT | | RUNNING). | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|