2005-09-07 00:00:00*** DENIED ***
 1) PLEASE SHOW WHICH SUB-SECTION OF
 SECTION 703 FBC/M 2001 YOU ARE USING
 TO OBTAIN COMBUSTION AIR FOR THE
 LAUNDRY ROOM.
 2) SUPPLY AIR DUCTS (MAIN TRUNK LINES &
 BRANCH LINES) ARE NOT PROPERLY SIZED
 FOR ADEQUATE AIR DISRIBUTION.
 3) RETURN AIR DUCTS TO AHU'S ARE NOT
 PROPERLY SIZED PER 2001 FBC/M 601.4.
 4) RETURN AIR GRILLS TO AHU'S ARE NOT
 SIZED (18"X18" WOULD BE TO SMALL).
 5) SUPPLY AIR DUCTS CAN NOT GO TO
 CLOSETS IN GARAGE (HAZARDOUS FUMES
 MAY ENTER DUCTS WHEN UNIT IS NOT
 RUNNING).