2005-08-31 00:00:00 | *********UNSAT 2ND REVIEW ****** |
| |
| PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| REVIEW AND SOME NEW COMMENTS DUE TO |
| CHANGES IN PLANS. |
| |
| 1)NOTE; 210.8A6,INDICATE GFI'S ALONG |
| KITCHEN COUNTERSPACES, REDLINED ONE. |
| SEE PLANS. |
| |
| 2)NOTE: PLEASE SEE NFPA-72, 8-1.4.2, |
| WHICH REQUIRES SD'S TO BE MIN OF 3' FROM |
| BATH DRS. |
| PLEASE SEE REDLINED PLANS FOR THESE. |
| PLEASE SEE "GREAT RMM" APPEARS TO SHOW |
| TWO SD'S ?? |
| THIS IS OK, BUT NOT REQUIRED.(FYI). |
| |
| 3)NOTE: PLEASE SHOW ALL SERVICE |
| EQUIPMENT ON PLANS CORRELATE WITH RISER |
| DIAGRAM SUBMITTED. |
| PLEASE SEE PLANS DO NOT SHOW LOCATION OF |
| METER/SERVICE. |
| PLEASE SEE TRANSFER SWITCH IS STILL |
| SHOWN ON PLANS, HOWEVER THIS HAS NOW |
| BEEN REMOVED FROM RISER? |
| |
| 4)NOTE:PLEASE SEE CIRCUITING FOR MIN |
| DINING RM, ETC RECEPTS WERE REVISED, |
| HOWEVER, PLEASE SEE CIRCUIT A-32 WHICH |
| SHARES BRKFAST AREA AND DEN AREA. |
| PLEASE SEE 210.52B1, OTHER OUTLETS MAY |
| NOT BE ON THESE CIRCUITS. |
| PLEASE SEE REDLINED RECEPTS ON PLANS IN |
| DEN. |
| |
| 5)NOTE: : PLEASE SEE REDLINED PLANS FOR |
| SOME RECEPTS MISSING FOR 2' OF WALL |
| SPACE AND WITH 6' OF DOORWAY. . |
| 210.52.2ND FLR. |
| |
| 6)NOTE:PLEASE CORRELATE LOAD |
| CALCUALTIONS NOW SUBMITTED. PLEASE SEE |
| THE LOADS SEEM TO HAVE BEEN ROUNDED DOWN |
| FOR EACH AND SERVICE. PLEASE SEE LOADS |
| MAY BE ROUNDED UP , BUT CAN BE ROUNDED |
| DOWN. |
| PLEASE SEE REDLINED PLANS. |
| PLEASE SEE POOL PANEL INDICATES 3.4KW |
| AND PANEL "B" SHOWS 4.2? |
| PLEASE SEE PANEL "A" SHOWS KW RATING FOR |
| PANEL "B" AS 15KW, HOWEVER PANEL "B" |
| INDICATES LOAD AT 39.9 WHICH DOES NOT |
| SEEM TO CORRELATE WITH LOAD CALCS OR |
| PANEL "A"? |
| PLEASE SEE 220.31. |
| |
| 7)NOTE: PLEASE SEE FS 553.80(2)(B), THIS |
| IS ONLY A NOTICE. |
| |
| PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. (ZONING ETC) |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| SETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SEE ALL OTHER COMMENTS FOR |
| GENERATOR WILL NOT BE INCLUDED. |
| PLEASE BE SURE TO SEE COMMENTS DUE TO |
| PLANNING FOR LOCATION OF FUTURE |
| EQUIPMNET. MAINS AND DISCONNECTING MEANS |
| SHALL BE GROUPED. |
| 230.72, 225.34, 225.31 |
| PLEASE CALL IF THERE ARE ANY QUESTIONS, |
| ON THIS. |
| |
| PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CAONTACTING |
| THIS OFFICE. |
| |