Date Text
2005-08-31 00:00:00*********UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 CHANGES IN PLANS.
  
 1)NOTE; 210.8A6,INDICATE GFI'S ALONG
 KITCHEN COUNTERSPACES, REDLINED ONE.
 SEE PLANS.
  
 2)NOTE: PLEASE SEE NFPA-72, 8-1.4.2,
 WHICH REQUIRES SD'S TO BE MIN OF 3' FROM
 BATH DRS.
 PLEASE SEE REDLINED PLANS FOR THESE.
 PLEASE SEE "GREAT RMM" APPEARS TO SHOW
 TWO SD'S ??
 THIS IS OK, BUT NOT REQUIRED.(FYI).
  
 3)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS CORRELATE WITH RISER
 DIAGRAM SUBMITTED.
 PLEASE SEE PLANS DO NOT SHOW LOCATION OF
 METER/SERVICE.
 PLEASE SEE TRANSFER SWITCH IS STILL
 SHOWN ON PLANS, HOWEVER THIS HAS NOW
 BEEN REMOVED FROM RISER?
  
 4)NOTE:PLEASE SEE CIRCUITING FOR MIN
 DINING RM, ETC RECEPTS WERE REVISED,
 HOWEVER, PLEASE SEE CIRCUIT A-32 WHICH
 SHARES BRKFAST AREA AND DEN AREA.
 PLEASE SEE 210.52B1, OTHER OUTLETS MAY
 NOT BE ON THESE CIRCUITS.
 PLEASE SEE REDLINED RECEPTS ON PLANS IN
 DEN.
  
 5)NOTE: : PLEASE SEE REDLINED PLANS FOR
 SOME RECEPTS MISSING FOR 2' OF WALL
 SPACE AND WITH 6' OF DOORWAY. .
 210.52.2ND FLR.
  
 6)NOTE:PLEASE CORRELATE LOAD
 CALCUALTIONS NOW SUBMITTED. PLEASE SEE
 THE LOADS SEEM TO HAVE BEEN ROUNDED DOWN
 FOR EACH AND SERVICE. PLEASE SEE LOADS
 MAY BE ROUNDED UP , BUT CAN BE ROUNDED
 DOWN.
 PLEASE SEE REDLINED PLANS.
 PLEASE SEE POOL PANEL INDICATES 3.4KW
 AND PANEL "B" SHOWS 4.2?
 PLEASE SEE PANEL "A" SHOWS KW RATING FOR
 PANEL "B" AS 15KW, HOWEVER PANEL "B"
 INDICATES LOAD AT 39.9 WHICH DOES NOT
 SEEM TO CORRELATE WITH LOAD CALCS OR
 PANEL "A"?
 PLEASE SEE 220.31.
  
 7)NOTE: PLEASE SEE FS 553.80(2)(B), THIS
 IS ONLY A NOTICE.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS. (ZONING ETC)
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SEE ALL OTHER COMMENTS FOR
 GENERATOR WILL NOT BE INCLUDED.
 PLEASE BE SURE TO SEE COMMENTS DUE TO
 PLANNING FOR LOCATION OF FUTURE
 EQUIPMNET. MAINS AND DISCONNECTING MEANS
 SHALL BE GROUPED.
 230.72, 225.34, 225.31
 PLEASE CALL IF THERE ARE ANY QUESTIONS,
 ON THIS.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CAONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW