Plan Review Notes
Plan Review Notes For Permit 05051108
Permit Number 05051108
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHT P2.2 THE SANITARY RISER DIAGRAM
 DOES NOT MEET CODE REQUIREMENTS. CORRECT
 THE FOLLOWING.
 A. VENT REQUIRED AT LAV FIRST FLOOR
 POWDER ROOM . SECTION 901.2.1
 B. CLEANOUT IS REQUIRED AT THE BASE OF
 THE STACK TO THE SECOND FLOOR. SECTION
 708.3.4.
 C. SIZE ALL PIPE SECTIONS PER TABLE
 710.1(1).
 D. VENTS ARE REQUIRED FOR BOTH KITCHEN
 SINKS. SECTION 901.2.1.
 E. VENTS REQUIRED FOR LAV NEAR THE
 GARAGE AND THE SINK IN THE GARAGE.
 SECTION 901.2.1.
 F. GARAGE SINK SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT OF THE POWDER
 ROOM FIXTURES. SECTION 909.1. SINK SHALL
 DISCHARGE DOWNSTREAM OF FIXTURES.
 G. VENT REQUIRED FOR THE SECOND FLOOR
 DOUBLE LAVS. SECTION 104.2.1.
 H. W/C AND TUB ARE NOT VENTED AS PIPED
 FOR BATHROOM WITH THE DOUBLE LAVS, AND
 THE WASH MACHINE SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT OF THAT
 BATHROOM. SECTIONS 901.2.1. & 909.1.
 I. VENTS ARE REQUIRED FOR THE TUB AND
 SINK NEAR AND AT THE GREAT ROOM. SECTION
 901.2.1.
 J. THE GREAT ROOM SINK SHALL NOT DRAIN
 THRU THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. THIS SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES. SECTION 909.1
 K. A VENT, A STANDPIPE AND A CLEANOUT
 ARE REQUIRED FOR THE WASH MACHINE. THE
 CLEANOUT SHALL BE LOCATED 4' ABOVE THE
 FLOOR. SECTIONS 708.10, 901.2.1 AND
 1002.1.
 L. VENTS ARE REQUIRED FOR BOTH LAVS IN
 THE MASTER BATHROOM. SECTION 901.2.1.
 M. FITTINGS CONNECTING THE ISLAND SINK
 IN THE KITCHEN AND THE TUB IN THE MASTER
 BATHROOM DO NOT GUIDE THE WASTE IN THE
 DIRECTION OF FLOW AS REQUIRED IN SECTION
 706.3.
 2. SEE RED LINE CORRECTIONS ON ONE SET
 OF PLANS AS AN EXAMPLE TO AID IN
 CORRECTING THE CODE VIOLATIONS.
 3. GAS INDICATED ON PLANS. SEPARATE
 PLANS AND PERMIT REQUIRED FOR GAS. SEE
 ATTACHED SHEET FOR GAS PERMIT
 APPLICATION REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]