Plan Review Notes
Plan Review Notes For Permit 05051108
Permit Number 05051108
Review Stop M
Sequence Number 1
Notes
Date Text
2005-06-15 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW;
 1.PLAN SHEET P2.1 INDICATES A GAS FIRE
 PLACE.PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL DATA.PROVIDE COMBUSTION AIR
 CALUCALTIONS AND MAKE-UP AIR (IF
 REQUIRED).
  
 2.PLAN SHEET P2.2 INDICATES A GAS
 DRYER.PLEASE PROVIDE CALCUALTIONS FOR
 COMBUSTION AIR AND AIR MAKE UP PER
 CHAPER 7 OF THE 2001 FBC(M).
  
 3.PLANS DO NOT INDICATE ACCESS OR
 HANGING DETAIL FOR THE AHU'S 1 & 2.
 SHOW COMPLAINCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 610.1.ABC.3.5.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.NOTE ON PLAN SHEET M2.1
 INDICATES THE REQUIREMENT FOR THE PAN
 BUT ONLY MENTIONS CONDENSATE LINE.
 SECONDARY DRAIN LINE SHALL TERMINATE AT
 A CONSPICUOUS POINT.
  
 5.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE
 PER 2001 FBC 1503.4.4.
  
 6.INDICATE LINE SIZE FOR THE
 CONDESATE, AND REFRIGERANT LINES.
  
 7.CONDENSING UNITS BE SUPPORTED BY A
 LEVEL CONCRETE SLAB A MINIMUM OF 3 1/2
 THICKEXTENDING A MINIMUM OF 2" ABOVE
 THE ADJOINING GRADE.
  
 8.PLANS DO NOT INDICATE TIE DOWN OR
 ANCHORING FOR THE CONDENSING UNIT.
 PLEASE REFERENCE 2001 FBC(M)301.13.1.
  
 9.PROVIDE GRILLE SIZES.ALSO MISSING
 RETURN AIR DUCT & JUMPER SIZES.PLEASE
 NOTE,SQUARE INCHES OF THE RETURN AIR
 JUMPERS ARE TO BE A MINIMUM OF 1 1/2
 TIMES GREATER THAN THE SUPPLY AIR INTO
 THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  