2005-06-15 00:00:00 | DENIED: |
| PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW; |
| 1.PLAN SHEET P2.1 INDICATES A GAS FIRE |
| PLACE.PLEASE PROVIDE MANUFACTURER'S |
| SUBMITTAL DATA.PROVIDE COMBUSTION AIR |
| CALUCALTIONS AND MAKE-UP AIR (IF |
| REQUIRED). |
| |
| 2.PLAN SHEET P2.2 INDICATES A GAS |
| DRYER.PLEASE PROVIDE CALCUALTIONS FOR |
| COMBUSTION AIR AND AIR MAKE UP PER |
| CHAPER 7 OF THE 2001 FBC(M). |
| |
| 3.PLANS DO NOT INDICATE ACCESS OR |
| HANGING DETAIL FOR THE AHU'S 1 & 2. |
| SHOW COMPLAINCE WITH 2001 FBC CHAPTER 13 |
| SUB-CHAPTER 610.1.ABC.3.5. |
| |
| 4.AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION REQUIRED PER 2001 |
| FBC(M)307.2.3.NOTE ON PLAN SHEET M2.1 |
| INDICATES THE REQUIREMENT FOR THE PAN |
| BUT ONLY MENTIONS CONDENSATE LINE. |
| SECONDARY DRAIN LINE SHALL TERMINATE AT |
| A CONSPICUOUS POINT. |
| |
| 5.CONDENSATE SHALL TERMINATE A MINIMUM |
| OF 12" AWAY FROM THE BUILDING STRUCTURE |
| PER 2001 FBC 1503.4.4. |
| |
| 6.INDICATE LINE SIZE FOR THE |
| CONDESATE, AND REFRIGERANT LINES. |
| |
| 7.CONDENSING UNITS BE SUPPORTED BY A |
| LEVEL CONCRETE SLAB A MINIMUM OF 3 1/2 |
| THICKEXTENDING A MINIMUM OF 2" ABOVE |
| THE ADJOINING GRADE. |
| |
| 8.PLANS DO NOT INDICATE TIE DOWN OR |
| ANCHORING FOR THE CONDENSING UNIT. |
| PLEASE REFERENCE 2001 FBC(M)301.13.1. |
| |
| 9.PROVIDE GRILLE SIZES.ALSO MISSING |
| RETURN AIR DUCT & JUMPER SIZES.PLEASE |
| NOTE,SQUARE INCHES OF THE RETURN AIR |
| JUMPERS ARE TO BE A MINIMUM OF 1 1/2 |
| TIMES GREATER THAN THE SUPPLY AIR INTO |
| THAT SPACE. |
| |