Date |
Text |
2005-06-07 00:00:00 | ********** UNSAT ************ |
| |
| 1)NOTE: PLEASE SEE PERMIT APPLICATION |
| MENTIONS "APPROACH AND DRIVEWAY FOR NEW |
| TWO STORY HOUSE" PLEASE ADJUST PERMIT |
| APPLICATION FOR NEW TWO STORY HOUSE. |
| |
| 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| PLEASE SEE AREA(S) TO BE INCLUDED AS |
| KITCHEN COUNTERSPACE AREA. |
| |
| 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| 8-1.4.2 |
| |
| 4)NOTE: PLEASE SEE MIN CLEARENCE |
| REQUIRED FOR A/C DISC'S. 110.26 |
| |
| 5)NOTE: PLEASE SHOW ALL SERVICE |
| EQUIPMENT ON PLANS. IF GENERATOR IS TO |
| BE INCLUDED UNDER ELECTRICAL PERMIT FOR |
| MAIN HOUSE. SITE PLAN, SURVEY ETC MUST |
| SHOW LOCATION OF GEN. ALSO. |
| PLEASE ALSO SEE OTHER COMMENTS FOR GEN |
| TO FOLLOW. |
| |
| 6)NOTE: PLEASE PROVIDE ROMM DESIGNATION |
| ON PLANS. |
| 215.5 |
| |
| 7)NOTE: PLEASE SEE CIRCUITING OF DINING |
| RM, BREAKFAST AREAS AND THE LIKE PER |
| 210.52-B-1. |
| |
| 8)NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| PLEASE SEE 210.12 2002NEC. |
| |
| 9)NOTE: PLEASE SEE ROOM ABOVE GARAGE. |
| PLEASE SEE RECEPTS WHICH APPEAR TO BE |
| FLOOR RECEPTS?? OR ARE THESE |
| MIS-LOCATED.? 210.52 |
| PLEASE ALSO SEE OTHER MISSING RECEPTS |
| MISSING FOR 2' OF WALL SPACE. |
| |
| 10)NOTE: PLEASE SEE CIRCUITING FOR BATH |
| GFI RECEPTS IN MASTER BATH. |
| PLEASE SEE 210.11C3, 210.52D |
| PLEASE SEE THERE SHALL BE NO OTHER |
| RECEPTS/OUTLETS EXCEPT FOR THOSE IN |
| BATHRM. |
| |
| 11)NOTE: PLEASE SEE PLANS INDICATE "SPA" |
| RECEPT FOR MASTER BATH. |
| PLEASE SEE PANEL SCHEDULE DOES NOT |
| INDICATE THIS. PLEASE ALSO ADJUST LOAD |
| CALCULATIONS TO INCLUDE LOAD AND PLEASE |
| SHOW AS GFI /GFI PROTECTED . |
| 215.5,220.31,680.71 |
| |
| 12)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| CALCULATIONS FOR EACH PANEL. |
| PLEASE CORRELATE LOADS ON PANEL |
| SCHEDULES AND SERVICE RISER LOAD CALCS. |
| PLEASE CORRELATE LOAD(S) FOR SUB |
| PANEL(S). PLEASE SEE PANEL "A" SHOWS THE |
| SAME LOAD AS SUB PANEL "B" , YET LOADS |
| IMPOSED ON EACH PANEL(BY PANEL SCHEDULE) |
| ARE COMPLETELY DIFFERENT. |
| 220,215.5 ETC. |
| PLEASE ALSO INCLUDE SIZE OF METERCAN TO |
| BE PROVIDED. |
| |
| 13)NOTE: PLEASE SEE SUB PANEL FOR POOL |
| IS MISSING FROM RISER, PANEL SCHEDULES |
| ETC.215.5 |
| |
| 14)NOTE: PLEASE CORRELATE DESCRIPTION |
| FOR PANEL "B". PLEASE SEE PANEL SHOWN AS |
| 42 CIR, HOWEVER PANEL MENTIONS 30?? |
| 215.5 |
| |
| 15)NOTE: PLEASE SEE 250.50 WHICH |
| REQUIRES THE "FOOTER STEEL" TO BE PART |
| OF THE GROUNDING ELECTRODE SYSTEM. |
| PLEASE SEE RISER MENTIONS STRUCTUAL |
| STEEL. IF THE CONSTRUCTION OF THE HOUSE |
| ALSO INCLUDES "STRUCTUAL STEEL" THEN IT |
| WOULD ALSO BE INCLUDED AS PART IF THE |
| GES. 250.50 |
| |
| PLEASE SEE THE FOLLOWING COMMENTS FOR |
| GEN/ATS ETC. |
| "IF" GENERATOR IS TO BE INCLUDED AS PART |
| OF THESE PLANS AND UNDER THE ELECTRICAL |
| PERMIT FOR THE HOUSE, THEN ALL OF THE |
| FOLLOWING INFORMATION MUST BE INCLUDED |
| WITH THIS PERMIT APPLICATION PACKAGE. |
| |
| |
| 16)NOTE: PLEASE SUBMIT COMLPETE SITE |
| PLAN SHOWING GEN LOCATIONS ALONG WITH |
| ANY OTHER EQUIPMENT WHICH MAY NEED TO BE |
| INCLUDED. THIS MUST ALSO BE INCLUDED ON |
| SURVEY SHOWING ALL DIMENIONS. |
| FUEL STORAGE TANK? ETC. |
| PLEASE ALSO SUBMIT ELEVATIONS FOR |
| EQUIPMENT WHICH MUST MUST BE ABOVE BASE |
| FLOOD ELEVATION. |
| 700.9 AND FEMA REGULATIONS OF UTILITY |
| EQUIPMENT. |
| |
| 17)NOTE: PLEASE INDICATE THE PRIME MOVER |
| FOR GEN. |
| 215.5,700.12B1-2 ETC |
| |
| 18)NOTE: PLEASE SEE STRUCTURAL DETAIL9S0 |
| MUST BE SUBMITTED FOR BLDG REVIEW FOR |
| ATTACHMENT OF GEN TO SLAB/ FBC 140MPH |
| WIND LOAD. |
| |
| 19)NOTE: PLEASE NOTE/KEEP IN MIND MIN |
| CLEARENCE FROM WINDOW/DOOR AND ATTIC |
| OPENINGS. A MIN OF 10" IS REQUIRED FOR |
| EXHAUST. SEE MECH CODE FOR MIN |
| REQUIREMENTS. THIS IS NOT AN ELECTRICAL |
| CODE. |
| |
| 20)NOTE: PLEASE SUBMIT COMPLETE |
| MANUFACTTURE CUT/SPEC SHEETS FOR |
| GENERATOR, AND ATS. |
| PLEASE BE SURE ALL MEET 702.3-702.6. |
| 225.31-225.36 |
| |
| 21)NOTE: PLEASE SEE MEANS OF DISC MUST |
| MEET 225.31-225.36. |
| NO DISC IS SHOWN ON LINE SIDE OF ATS. |
| NO INFORMATION FOR ATS IS PROVIDED. |
| SIZE? |
| PLEASE SEE THE MEANS OF DISC IS REQUIRED |
| TO BE LOCATED ADJACENT TO OR BACK TO |
| BACK WITH TRANSFER SWITCH. |
| 215.5 |
| |
| 22)NOTE: PLEASE CORRELATE PLANS WITH |
| RISER DIAGRAM. PLEASE SEE PLANS MENTIOSN |
| AN ATS (AUTOMATIC TRANSFER SWITCH) YET |
| RISER MENTIONS A MANUAL TRANSFER |
| SWITCH(MTS). |
| PLEASE SEE 702.5, IF SYSTEM IS GOING TO |
| BE AN "AUTOMATIC" SYSTEM, THEN GEN. IS |
| REQUIRED TO BE SIZED FOR SERVICE/LOAD |
| CALCULATIONS AS SHOWN. |
| MEANS OF LOAD SHEEDING (IF) PROVIDED |
| WOULD NEED TO BE SHOWN IN DETAIL. |
| 215.5 |
| |
| 23)NOTE: PLEASE INCLUDE CONDUCTORS FROM |
| TRANSFER SWITCH TO MCB PANEL. |
| PLEASE SEE 250.24, 250.6 IF FIRST MEANS |
| OF DISC IS PROVIDED. |
| |
| 24)NOTE: PLEASE BE SURE TO NOTE WHEATHER |
| OR NOT GEN IS TO BE SEPARATELY DERIVED |
| OR NOT.. |
| |
| PLEASE SEE MANY OF THE ABOVE LOCATIONS |
| HAVE BEEN REDLIND ON ONE SET OF PLANS |
| FOR COMMENTS ABOVE. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE SUBMIT "ONE" SET OF OLD/VOIDED |
| SHEETS FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |