Plan Review Notes
Plan Review Notes For Permit 05051108
Permit Number 05051108
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-07 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS "APPROACH AND DRIVEWAY FOR NEW
 TWO STORY HOUSE" PLEASE ADJUST PERMIT
 APPLICATION FOR NEW TWO STORY HOUSE.
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE SEE AREA(S) TO BE INCLUDED AS
 KITCHEN COUNTERSPACE AREA.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 8-1.4.2
  
 4)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED FOR A/C DISC'S. 110.26
  
 5)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS. IF GENERATOR IS TO
 BE INCLUDED UNDER ELECTRICAL PERMIT FOR
 MAIN HOUSE. SITE PLAN, SURVEY ETC MUST
 SHOW LOCATION OF GEN. ALSO.
 PLEASE ALSO SEE OTHER COMMENTS FOR GEN
 TO FOLLOW.
  
 6)NOTE: PLEASE PROVIDE ROMM DESIGNATION
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SEE CIRCUITING OF DINING
 RM, BREAKFAST AREAS AND THE LIKE PER
 210.52-B-1.
  
 8)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 210.12 2002NEC.
  
 9)NOTE: PLEASE SEE ROOM ABOVE GARAGE.
 PLEASE SEE RECEPTS WHICH APPEAR TO BE
 FLOOR RECEPTS?? OR ARE THESE
 MIS-LOCATED.? 210.52
 PLEASE ALSO SEE OTHER MISSING RECEPTS
 MISSING FOR 2' OF WALL SPACE.
  
 10)NOTE: PLEASE SEE CIRCUITING FOR BATH
 GFI RECEPTS IN MASTER BATH.
 PLEASE SEE 210.11C3, 210.52D
 PLEASE SEE THERE SHALL BE NO OTHER
 RECEPTS/OUTLETS EXCEPT FOR THOSE IN
 BATHRM.
  
 11)NOTE: PLEASE SEE PLANS INDICATE "SPA"
 RECEPT FOR MASTER BATH.
 PLEASE SEE PANEL SCHEDULE DOES NOT
 INDICATE THIS. PLEASE ALSO ADJUST LOAD
 CALCULATIONS TO INCLUDE LOAD AND PLEASE
 SHOW AS GFI /GFI PROTECTED .
 215.5,220.31,680.71
  
 12)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR EACH PANEL.
 PLEASE CORRELATE LOADS ON PANEL
 SCHEDULES AND SERVICE RISER LOAD CALCS.
 PLEASE CORRELATE LOAD(S) FOR SUB
 PANEL(S). PLEASE SEE PANEL "A" SHOWS THE
 SAME LOAD AS SUB PANEL "B" , YET LOADS
 IMPOSED ON EACH PANEL(BY PANEL SCHEDULE)
 ARE COMPLETELY DIFFERENT.
 220,215.5 ETC.
 PLEASE ALSO INCLUDE SIZE OF METERCAN TO
 BE PROVIDED.
  
 13)NOTE: PLEASE SEE SUB PANEL FOR POOL
 IS MISSING FROM RISER, PANEL SCHEDULES
 ETC.215.5
  
 14)NOTE: PLEASE CORRELATE DESCRIPTION
 FOR PANEL "B". PLEASE SEE PANEL SHOWN AS
 42 CIR, HOWEVER PANEL MENTIONS 30??
 215.5
  
 15)NOTE: PLEASE SEE 250.50 WHICH
 REQUIRES THE "FOOTER STEEL" TO BE PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SEE RISER MENTIONS STRUCTUAL
 STEEL. IF THE CONSTRUCTION OF THE HOUSE
 ALSO INCLUDES "STRUCTUAL STEEL" THEN IT
 WOULD ALSO BE INCLUDED AS PART IF THE
 GES. 250.50
  
 PLEASE SEE THE FOLLOWING COMMENTS FOR
 GEN/ATS ETC.
 "IF" GENERATOR IS TO BE INCLUDED AS PART
 OF THESE PLANS AND UNDER THE ELECTRICAL
 PERMIT FOR THE HOUSE, THEN ALL OF THE
 FOLLOWING INFORMATION MUST BE INCLUDED
 WITH THIS PERMIT APPLICATION PACKAGE.
  
  
 16)NOTE: PLEASE SUBMIT COMLPETE SITE
 PLAN SHOWING GEN LOCATIONS ALONG WITH
 ANY OTHER EQUIPMENT WHICH MAY NEED TO BE
 INCLUDED. THIS MUST ALSO BE INCLUDED ON
 SURVEY SHOWING ALL DIMENIONS.
 FUEL STORAGE TANK? ETC.
 PLEASE ALSO SUBMIT ELEVATIONS FOR
 EQUIPMENT WHICH MUST MUST BE ABOVE BASE
 FLOOD ELEVATION.
 700.9 AND FEMA REGULATIONS OF UTILITY
 EQUIPMENT.
  
 17)NOTE: PLEASE INDICATE THE PRIME MOVER
 FOR GEN.
 215.5,700.12B1-2 ETC
  
 18)NOTE: PLEASE SEE STRUCTURAL DETAIL9S0
 MUST BE SUBMITTED FOR BLDG REVIEW FOR
 ATTACHMENT OF GEN TO SLAB/ FBC 140MPH
 WIND LOAD.
  
 19)NOTE: PLEASE NOTE/KEEP IN MIND MIN
 CLEARENCE FROM WINDOW/DOOR AND ATTIC
 OPENINGS. A MIN OF 10" IS REQUIRED FOR
 EXHAUST. SEE MECH CODE FOR MIN
 REQUIREMENTS. THIS IS NOT AN ELECTRICAL
 CODE.
  
 20)NOTE: PLEASE SUBMIT COMPLETE
 MANUFACTTURE CUT/SPEC SHEETS FOR
 GENERATOR, AND ATS.
 PLEASE BE SURE ALL MEET 702.3-702.6.
 225.31-225.36
  
 21)NOTE: PLEASE SEE MEANS OF DISC MUST
 MEET 225.31-225.36.
 NO DISC IS SHOWN ON LINE SIDE OF ATS.
 NO INFORMATION FOR ATS IS PROVIDED.
 SIZE?
 PLEASE SEE THE MEANS OF DISC IS REQUIRED
 TO BE LOCATED ADJACENT TO OR BACK TO
 BACK WITH TRANSFER SWITCH.
 215.5
  
 22)NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLEASE SEE PLANS MENTIOSN
 AN ATS (AUTOMATIC TRANSFER SWITCH) YET
 RISER MENTIONS A MANUAL TRANSFER
 SWITCH(MTS).
 PLEASE SEE 702.5, IF SYSTEM IS GOING TO
 BE AN "AUTOMATIC" SYSTEM, THEN GEN. IS
 REQUIRED TO BE SIZED FOR SERVICE/LOAD
 CALCULATIONS AS SHOWN.
 MEANS OF LOAD SHEEDING (IF) PROVIDED
 WOULD NEED TO BE SHOWN IN DETAIL.
 215.5
  
 23)NOTE: PLEASE INCLUDE CONDUCTORS FROM
 TRANSFER SWITCH TO MCB PANEL.
 PLEASE SEE 250.24, 250.6 IF FIRST MEANS
 OF DISC IS PROVIDED.
  
 24)NOTE: PLEASE BE SURE TO NOTE WHEATHER
 OR NOT GEN IS TO BE SEPARATELY DERIVED
 OR NOT..
  
 PLEASE SEE MANY OF THE ABOVE LOCATIONS
 HAVE BEEN REDLIND ON ONE SET OF PLANS
 FOR COMMENTS ABOVE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT "ONE" SET OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved