2005-05-16 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PRODUCT APPROVAL SUBMITTED WAS
 REVISED FROM ONE SUBMITTED AT TIME OF
 BLDG PERMIT APPLICATION. PRODUCT
 APPROVAL SUBMITTED AT THAT TIME WAS
 APPROVED BECAUSE IT WAS GOOD FOR UP TO
 -92PSF MAX. DESIGN PRESSURE. PRODUCT
 APPROVAL SUBMITTED NOW IS GOOD FOR UP TO
 -57PSF DESIGN PRESSURE. ACCORDING TO
 TABLE 1606.2B FLORIDA BUILDING CODE 2001
 ROOF ZONES 2 AND 3 NEED TO RESIST
 PRESSURES TO -68.1PSF. PRODUCT APPROVAL
 SUBMITTED IS GOOD UP TO -57.5 PSF DESIGN
 PRESSURE.
 SYSTEM LIMITATIONS ON PAGE 5 OF 5 OF
 PRODUCT APPROVAL SAYS THAT FASTENING
 ENHANCING BY RATIONAL ANALYSIS TO BE
 DONE BY ENGINEER, ARCHITECT OR
 REGISTERED ROOF CONSULTANT. PROVIDE
 RATIONAL ANALYSIS AS REQUIRED.
  
 2- POLYSTICK UNDERLAYMENT IS DESIGNED
 FOR TILE UNDERLAYMENT, NOT METAL. SEE
 POLYSTIC PRODUCT DESCRIPTION.
 SEE METAL ROOF SYSTEM PRODUCT APPROVAL
 FOR REQUIRED UNDERLAYMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.