Plan Review Notes For Permit 05051068 |
Permit Number |
05051068 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-04 00:00:00 | DENIED; | | 1. | | 1) COMPLY WITH FBC-2001 SEC 424.2 | | PRIVATE SWIMMING POOLS. | | 2.FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE( ADD TO NOTES.) | | 3.FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 4.FBC-2001 424.2.13.2 JOINTS AND | | CONNECTIONS, FBC PLUM SEC 605.21 PURPLE | | PRIMER REQUIRED ONB PIPING. ( ADD TO | | NOTES) | | 5. CONNECTIONS TO WATER HEATING | | EQUIPMENT SHALLBE INSTALLED WITH FLANGES | | OR UNIONS CONNECTIONS ADJACENT TO THE | | HEATER. (ADD TO NOTES) | | 6.GAS PIPING SHALL COMPLY WITH FBC FUIL | | GAS SEPARATE [LANS AND PERMIT REQUIRED. | | (ADD TO NOTES) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|