Plan Review Notes
Plan Review Notes For Permit 05050580
Permit Number 05050580
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SMOKE DETECTORS ARE REQUIRED PER
 905.2.2 FBC. INSIDE AND OUTSIDE OF
 BEDROOMS, CLOSE PROXIMITY OF STAIRS.
  
 2} THE 200 AMP SERVICE IS NOT LARGE
 ENOUGH FOR THE 203.5 AMP CALCULATED
 LOAD. SERVICE SAMPERAGE SIZE NEEDS TO BE
 INCREASED PER ARTICLE 220.
  
 3} THE SMALL APPLIANCE CIRCUITS MUST BE
 CALCULATED AT 1500 VA EACH PER
 220.16(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  