Date |
Text |
2005-07-19 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SMOKE DETECTORS ARE REQUIRED PER | | 905.2.2 FBC. INSIDE AND OUTSIDE OF | | BEDROOMS, CLOSE PROXIMITY OF STAIRS. | | | | 2} THE 200 AMP SERVICE IS NOT LARGE | | ENOUGH FOR THE 203.5 AMP CALCULATED | | LOAD. SERVICE SAMPERAGE SIZE NEEDS TO BE | | INCREASED PER ARTICLE 220. | | | | 3} THE SMALL APPLIANCE CIRCUITS MUST BE | | CALCULATED AT 1500 VA EACH PER | | 220.16(A). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|