2005-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT 1 SANITARY RISER DIAGRAMS.
 CORRECT THE FOLLOWING:
 A. BIDET IS NOT VENTED. SECTION 901.2.1
 B. CLEANOUT REQUIRED 4' ABOVE THE FLOOR
 SECTION 708.10
 C. SHOW ALL PIPE SIZES. TABLE 710.1(1)
 2. ALL SHEETS ARCHITECT LICENSE NUMBER
 IS REQUIRED IN TITLE BLOCK.
 61G1-16.004(2) AND FS 481.2055
  