Plan Review Notes For Permit 05050580 |
Permit Number |
05050580 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-23 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE RISER MUST INDICATE CONDUIT AND | | WIRE SIZE AND TYPE. | | | | 2} INDICATE WHICH DEVICES ARE EXISTING | | AND WHICH ARE BEING ADDED ON THE PLAN. | | | | 3} PLEASE SEE 210.8(A)(6) REGARDING | | KITCHEN COUNTERTOP GFI'S AND 210.11(C) | | FOR SPACING. | | | | 4} INDICARE IF ELECTRICAL WORK IS BEING | | DONE ON THE 2ND FLOOR. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|