Plan Review Notes
Plan Review Notes For Permit 05050464
Permit Number 05050464
Review Stop P
Sequence Number 5
Notes
Date Text
2005-11-19 00:00:00DENIED;
 1. BREAK SINK NOT SHOWN ON SANITARY
 RISER DIAGRAM.
 2.WATER RISER PIPING IS NOT SIZED, SHOCK
 ARRESTORS FOR BREAK SINK ARE MISSING,
 WATER SEVICE IS PIPED WRONG AT HEATER
 AND SHUTOFF VALVE IS NOT SHOWN.
 3.WATER RISER DIAGRAM SHOWS HOT AND COLD
 WATER TO BREAK SINK, AND ALSO HAS A NOTE
 AT THE SINK CALLING FORINSTA HOT
 PLEASE CORRECT.
 4.OLD RISER DIAGRAM SHOWED NOTE SAID
 "TIE INTO EXISTINGBUILDING SANITARY AT
 RESTROOMS ABOVE 6TH FLOOR CEILING",
 REVISED PLAN READS,"ABOVE 5TH FLOOR
 CEILING. SUITE IS ON THE 7TH FLOOR. THE
 EXISTING 4" SANITARY PIPE AT BATHROOMS
 SHOULD NOT BE CAPPED OFF, THAT STACK
 BECOMES A VENT ON THE TOP FLOOR AND GOES
 OUT THE ROOF.
 ONE SET OF DRAWINGS MARKED IN RED.
 PLUMBING PLAN REVIED BY;
 JOHN LEECH
 805-6695
  
  
  
  
  
  
  
  
  
  
  
  