Plan Review Notes
Plan Review Notes For Permit 05050464
Permit Number 05050464
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-07 00:00:00******** UNSAT *********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 AND SOME CHANGES IN PLANS HAVE COMMENTS.
  
 1)NOTE: PLEASE SEE NOTE#1 FROM PREVIOUS
 REVIEWED REQUESTED THE ENGINEER
 RESPONSIBLE FOR DESIGN TO SIGN AND SEAL
 PLANS. THIS WAS DONE, HOWEVER ENGINEER'S
 TITLE BLOCK WAS REMOVED??
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.023 FOR REQUIRED TITLEBLOCK AND
 INFORMAITON REQUIRED ON SAID TITLE
 BLOCK.
  
 2)NOTE: PLEASE SEE RISER DIGRAM HAS NOW
 BEEN REVISED, PLEASE SEE PANEL "LB" IS
 STILL SHOWN AS MLO. PLEASE SEE RISER
 MENTIONS 175A BRKR. PLEASE SEE PANEL
 "LA" INDICATES BEING A 225A MCB? PLEASE
 CORRELATE.
 PLEASE SEE PANEL "LB" DOES NOT INDICATE
 ANY OCP FEEDING "LA"? IS THIS A FEED
 THRU LUGS PANEL?
 408.16,240.21 ETC.
  
 3)NOTE: PLEASE SEE PANEL 4H STILL
 INDICATES 200A OCP FEEDING 45KVA
 TRANSFORMER? ON #6 AWG.
 PLEASE SEE MAX OCP IN 450.3(125%).
 PLEASE ALSO SEE 240.4,310.16 FOR SIZING
 OF CONDUCTORS.
  
 4)NOTE: PLEASE SEE 210.8B3 FOR
 KITCHEN/BRK RM RECEPTS WHICH REQUIRES
 ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETSFOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  