Date |
Text |
2005-07-07 00:00:00 | ******** UNSAT ********* |
| |
| PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| AND SOME CHANGES IN PLANS HAVE COMMENTS. |
| |
| 1)NOTE: PLEASE SEE NOTE#1 FROM PREVIOUS |
| REVIEWED REQUESTED THE ENGINEER |
| RESPONSIBLE FOR DESIGN TO SIGN AND SEAL |
| PLANS. THIS WAS DONE, HOWEVER ENGINEER'S |
| TITLE BLOCK WAS REMOVED?? |
| PLEASE SEE FAC 61G15-23.002 AND FS |
| 471.023 FOR REQUIRED TITLEBLOCK AND |
| INFORMAITON REQUIRED ON SAID TITLE |
| BLOCK. |
| |
| 2)NOTE: PLEASE SEE RISER DIGRAM HAS NOW |
| BEEN REVISED, PLEASE SEE PANEL "LB" IS |
| STILL SHOWN AS MLO. PLEASE SEE RISER |
| MENTIONS 175A BRKR. PLEASE SEE PANEL |
| "LA" INDICATES BEING A 225A MCB? PLEASE |
| CORRELATE. |
| PLEASE SEE PANEL "LB" DOES NOT INDICATE |
| ANY OCP FEEDING "LA"? IS THIS A FEED |
| THRU LUGS PANEL? |
| 408.16,240.21 ETC. |
| |
| 3)NOTE: PLEASE SEE PANEL 4H STILL |
| INDICATES 200A OCP FEEDING 45KVA |
| TRANSFORMER? ON #6 AWG. |
| PLEASE SEE MAX OCP IN 450.3(125%). |
| PLEASE ALSO SEE 240.4,310.16 FOR SIZING |
| OF CONDUCTORS. |
| |
| 4)NOTE: PLEASE SEE 210.8B3 FOR |
| KITCHEN/BRK RM RECEPTS WHICH REQUIRES |
| ALL 15- AND 20-AMPERE, 125-VOLT |
| RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| TO BE GFCI PROTECTED. THIS REQUIREMENT |
| APPLIES TO EACH AND EVERY 15- AND |
| 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| WHETHER OR NOT THE RECEPTACLE SERVES |
| COUNTERTOP APPLIANCES. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETSFOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |