2005-05-20 00:00:00 | ********UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE PLANS ARE CONTAINING |
| A TITLE BLOCK OF SORTS WHICH REFERENCE A |
| PE FOR PLANS, HOWEVER THE PE SHOWN HAS |
| NOT SIGNEDAND SEALED PLANS.?? |
| PLEASE SEE IF PE IS RESPONSIBLE FOR |
| DESIGNAND ON PLANS , THEN THAT PE MUST |
| SIGN,DATE AND SEALED PLANS. FS471.025 |
| |
| PLEASE SEE SEAL FOR ARCH (IF ARCH SEALS |
| PLANS) IS CLEAR AND VISABLE WIH |
| INFORMATION REQUIRED ON SEAL FOR P, M |
| AND E SHEETS. |
| FS 481.221 FAC 61G1-16.003 |
| |
| 2)NOTE: PLEASE CLARIFY MEANS OF DISC AND |
| OCP FROM BUS RISER? |
| PLEASE SEE 4H IS SHOWN AS MLO? THERE |
| SHALL BE A MAIN AND OCP ON THE LINE SIDE |
| 4H. |
| PLEASE SEE PANELS ON THE SECONDARY SIDE |
| OF THE TRANSFORMER ARE BOTH SHOWN AS |
| MLO. |
| PLEASE SEE THESE SHALL BOTH HAVE MCB'S |
| INSTALLED. |
| 215.5,408.16,240.21 ETC. |
| |
| 3)NOTE: PLEASE SEE 200A OCP SHOWN FOR |
| MAIN SIDE OF 45 KVA TRANSFORMER DOES NOT |
| MEET 450.3. A MAX OCP OF 125% IS ONLY |
| PERMITTED. |
| |
| PLEASE BE SURE TO SEE ANY POSSIBLE |
| COMMENTS FROM OTHER REVIEWER(S) WHICH |
| MAY AFFECT ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AN |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |