Plan Review Notes
Plan Review Notes For Permit 05050464
Permit Number 05050464
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-20 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS ARE CONTAINING
 A TITLE BLOCK OF SORTS WHICH REFERENCE A
 PE FOR PLANS, HOWEVER THE PE SHOWN HAS
 NOT SIGNEDAND SEALED PLANS.??
 PLEASE SEE IF PE IS RESPONSIBLE FOR
 DESIGNAND ON PLANS , THEN THAT PE MUST
 SIGN,DATE AND SEALED PLANS. FS471.025
  
 PLEASE SEE SEAL FOR ARCH (IF ARCH SEALS
 PLANS) IS CLEAR AND VISABLE WIH
 INFORMATION REQUIRED ON SEAL FOR P, M
 AND E SHEETS.
 FS 481.221 FAC 61G1-16.003
  
 2)NOTE: PLEASE CLARIFY MEANS OF DISC AND
 OCP FROM BUS RISER?
 PLEASE SEE 4H IS SHOWN AS MLO? THERE
 SHALL BE A MAIN AND OCP ON THE LINE SIDE
 4H.
 PLEASE SEE PANELS ON THE SECONDARY SIDE
 OF THE TRANSFORMER ARE BOTH SHOWN AS
 MLO.
 PLEASE SEE THESE SHALL BOTH HAVE MCB'S
 INSTALLED.
 215.5,408.16,240.21 ETC.
  
 3)NOTE: PLEASE SEE 200A OCP SHOWN FOR
 MAIN SIDE OF 45 KVA TRANSFORMER DOES NOT
 MEET 450.3. A MAX OCP OF 125% IS ONLY
 PERMITTED.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AN
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  