Plan Review Notes For Permit 05050390 |
Permit Number |
05050390 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-09 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6716 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC 1606.2.5THE SYSTEM SELECTED | | FROM THE SUBMITTED FLAT ROOF PRODUCT | | APPROVAL NOA HAS A MAXIMUM DESIGN | | PRESSURE OF LESS THAN -89 PSF AND CITES | | GENERAL LIMITATION #9 (SEE PAGE 7, 30 & | | 31 OF 34).GENERAL LIMITATION #9 | | PROHIBITS RATIONAL ANALYSIS OR | | EXTRAPOLATION TO ENHANCE THE UPLIFT | | PRESSURE AT PERIMETER AND CORNER AREAS | | BY REDUCING THE FASTENER SPACING IN | | THESE AREAS.EITHER SELECT AN | | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) | | THAT DOES NOT CITE GENERAL LIMITATION | | #9.ALTERNATIVELY IF THE SELECTED | | SYSTEM DOES CITE GENERAL LIMITATION #9, | | IT MUST HAVE A MAXIMUM DESIGN PRESSURE | | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 | | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT | | OF 30 FEET OR LESS). | | |
|