2005-05-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1. FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON THE | | WATER SERVICE. (ADD TO NOTES) | | 2. FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3. FBC-2001 424.2.13.2 JOINTS AND | | CONNECTIONS, FBC PLMG. SEC 605.21 PURPLE | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | NOTES). | | 4. MANUF. SPECIFICATION SHEETS DO NOT | | SHOW POSITIVE MEANS TO RETAIN WATER | | SHOULD THE PUMP SHUT OFF. AN EXTERIOR | | HARTFORD LOOP IS REQUIRED. SECTION | | 424.2.14.2 | | 5. FBC-2001 424.2.15 GAS PIPING SHALL | | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS | | AND PERMIT REQUIRED. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|