2005-08-28 00:00:00 | PLUMBING PLAN REVIEW EXAMINER, FBC 2001 |
| PAUL SCHMITZ561-805-6692 |
| |
| [email protected] |
| FBC 2001 |
| DENIED |
| 1.PREVIOUS REVIEW: |
| PLAN REVIEW COMMENTS SHALL BE RESPONDED |
| TO BY THE DESIGN PROFESSIONALS. REFERING |
| TO EACH OTHER OR CONTRACTOR, IS NOT |
| HELPFUL IN EXPEDITING YOUR PERMIT. |
| 2. PLANS SHALL BE ROUTED TO THE PALM |
| BEACH COUNTY HEALTH UNIT DIVISION OF |
| ENVIROMENTAL HEALTH FOR REVIEW PRIOR TO |
| RESUBMITTING. EACH SET OF PLANS |
| RESUBMITTED FOR REVIEW BY CITY WPB SHALL |
| BE STAMPED BY HEALTH DEPT REVIEWER. |
| SECTION 101.4.7.- FOOD SERVICE. |
| 3. GREASE INTERCEPTOR: IF REQUIRED SHALL |
| BE SIZED BY THE ENVIRONMENTAL COMPLIANCE |
| MANAGER.WASTE ORD #2938-96 OR #3434. |
| PLEASE CONTACT LYNN MASSON |
| (561)822-2271, BY E-MAIL |
| [email protected], OR FAX (561)822-22792 |
| 4. SHT A-3 THE FOLLOWING INFORMATION FOR |
| CHAPTER 11 SHALL BE SHOWN OR INDICATED |
| ON THE PLANS: |
| FOR WATER CLOSETS: (SHT A-3 STALLS) |
| GRAB BARS, IN STALLS, 42" SHALL BE ON |
| THE LONG SIDE, 36" GRAB BARS ON SHORT |
| SIDE. |
| FOR URINAL: (SHT A-3 NOT ADDRESSED) |
| A. 11-4.18.2 HEIGHT |
| B. 11-4.18.3 CLEAR FLOOR SPACE |
| C. 11-4.18.4 FLUSH CONTROLS |
| FOR SHOWERS: SHT A-3 |
| E. 11-4.21.7 CURBS (SHALL BE NO HIGHER |
| THAN 1/2") |
| DRINKING FOUNTAIN:( YOUR COMMENT ABOUT |
| YOUNG PEOPLE, AND THEIR AGE, DOES NOT |
| EXEMPT YOU FROM COMPLING WITH, CH 11 FL |
| ACCESSIBILITY CODE) |
| A. 11-4.15.2 SPOUT HEIGHT |
| B. 11-4.15.3 SPOUT LOCATION |
| C. 11-4.15.4 CONTROLS |
| D. 11-4.15.5 CLEARANCES/CLEAR FLOOR |
| SPACE |
| E. 11-4.1.3(10)(A) FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. (IF THIS |
| IS A SINGLE ELEVATION UNIT - NOT |
| REQUIRED IF HIGH/LOW DRINKING FOUNTAIN). |
| 8. AN RPZ BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE TO THE BUILDING. SECTION |
| 608.13.2. |
| |
| 5. AN RPZ BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE TO THE BUILDING. SECTION |
| 608.13.2. ( NO CIVIL PLANS WITH THIS |
| SUBMITTAL) |
| END OF COMMENTS |