2005-08-27 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05050354 |
| ADD: 3700 BROADWAYY |
| CONT: WEST |
| TEL: (561)718-8656 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| |
| |
| 1) COMMENT# 3) FROM THE PREVIOUS REVIEW, |
| PROVIDE ADDITIONAL INFORMATION, |
| PROVIDE MIN. BUILDING TYPE OF DESIGN, |
| (TABLE 500/ 600) IF ANY AREA INCREASES |
| WERE TAKEN? PLANS INDICATE THIS TO BE A |
| TYPE IV/ 1 HR PROTECTED/ FULLY |
| SPRINKLERED BUILDING. |
| 1A) FOR THIS BUILDING TO BE CONSIDERED |
| TYPE IV CONSTRUCTION, LOOK AT TABLE 600, |
| NON BEARING WALLS, NO COMBUSTIBLE IN |
| WALLS SHEET A-4 STILL INDICATES THE USE |
| OF PLYWOOD AS A SUBSHEATHING. THIS |
| BUILDING CAN BE CONSIDERED A TYPE VI |
| UNPROTECTED/ FULLY SPRINKLERED BUILDING, |
| THIS WILL ALLOW THE WOOD INFILL IN THE |
| EXTERIOR WALLS AND PROVIDE AN ALLOWABLE |
| 24,000 SQ FT BUILDING. |
| 1B) CLASSIFICATION OF THIS BUILDING AS A |
| TYPE IV 1HR PROTECTED BUILDING ALSO |
| CREATES A PROBLEM WITH THE ROOF |
| SHEATHING, TABLE 600 REQUIRES THEROOF TO |
| BE 1 HR RATED, FOOTNOTE "E" DOES ALLOW |
| ONE STORY BUILDINGS TO USE FIRE |
| RETARDANT WOOD SHEATHING. TYPE VI |
| UNPROTECTED/ FULLY SPRINKLERED HAS NO |
| SUCH LIMITATIONS WITH THE ROOF. |
| |
| 2) COMMENT 6B FROM THE PREVIOUS REVIEW, |
| 6B)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 6C)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| ******* E) ROOF ASSEMBLIES MISSING FL |
| COVER SHEET, NOA GOOD FOR STEEL DECK |
| PLANS INDICATE T&G DECK.**************** |
| |
| 3) ALTHOUGH THE ENERGY CALCULATIONS ARE |
| SEALED THEY INDICATE THE WORK BEING |
| COMPLETED IS IN RIVIERA. |
| |
| 4) COMENT# 8 FROM THE PREVIOUS |
| REVIEWDEALS WITH INFILL FOR THE EXTERIOR |
| WALLS, DEPENDING ON THE RESULTS OF |
| QUESTION # 1 THIS MAY OR MAY NOT BE A |
| ISSUE. SHEET A-4, FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| 4A) EXTERIOR WALL DETAILS INDICATE THE |
| USE OF WOOD INFILL, DEPENDING ON THE |
| CLASSIFICATION OF THIS BUILDING THIS MAY |
| BE A ISSUE. THE ITEMS IN CONCERN ARE THE |
| DESIGNER OF RECORD DOES NOT INDICATE HOW |
| THE 2X8 PT PLATE WILL BE ANCHORED INTO |
| THE EXISTING STRUCTURE? |
| |
| 5) PLEASE PROVIDE FIRE SPRINKLER PLANS |
| OF EXISTING SYSTEM AND IF ANY NEW HEADS |
| ARE BEING INSTALLED. PLANS WILL BE |
| REQUIRED SINCE IT APPEARS THAT YOU ARE |
| TAKING THE EXCEPTION TO 1005.4.2 |
| EXECEPTION (1) |
| 1. EMERGENCY ESCAPE AND RESCUE OPENINGS |
| SHALL NOT BE REQUIRED IN BUILDINGS |
| PROTECTED THROUGHOUT BY AN APPROVED |
| AUTOMATIC SPRINKLER SYSTEM. |
| |
| 6) NEW COMMENT THE ORIENTATION OF |
| BROADWAY IS ON THE WRONG SIDE OF THE |
| BUILDING, CORRECTING WILL HELP IN TABLE |
| 600 ISSUES, SEE A-1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |