2005-06-23 00:00:00 | DENIED: |
| 1.PLAN SHEET AC-1 DUCT PENTRATING WALL |
| BETWEEN THE STORAGE ROOM AND CLASS ROOM |
| #6 INDICATES A FIRE DAMPER.ACCORDING |
| TO PLAN SHEET A-2 THE FIRE DAMPER SHOULD |
| BE LOCATED BETWEEN THE CORRIDOR AND THE |
| STORAGE ROOM, PLEASE CLARIFY. |
| |
| 2.PROVIDE CURB DETAIL & TERMINATION |
| LOCATION FOR EXHAUST FANS.PROVIDE |
| DISTANCE FROM FRESH AIR INTAKES ON THE |
| RTU'S. |
| |
| 3.PROVIDE INFORMATION FOR EXHAUST DUCT |
| TO THE DRYER LOCATED IN THE "HOUSEHOLD |
| ROOM".INDICATE DUCT SIZE, MATERIAL, |
| AND TERMINATION.PLEASE NOTE, PER 2001 |
| FBC(M) 504.6, MAKEUP AIR SHALL BE |
| PROVIDED FOR INTALLATIONS THAT EXHAUST |
| GREATER THAN 200 CFM. |
| |
| 4.PLAN SHEET AC-1 INDICATES RETURN AIR |
| IN THE LAUNDRY AREA.WILL THIS BE |
| RECIRCULATED? |
| |
| 5.PROVIDE SPECIFICATION ON THE DRYER. |
| |
| 6.INDICATE WHAT KIND OF FOOD PREP WILL |
| BE TAKING PLACE.PLAN SHEET A-2 |
| INDICATES HOT & COLD FOOD.PLEASE |
| INDICATE ANY "COOKING" EQUIPMENT OR |
| APPLIANCES. |
| |
| 7.PLAN SHEET AC-1 INDICATES |
| DISHWASHER, PLEASE PROVIDE SUBMITTAL |
| DATA.WILL A HEAT HOOD BE REQUIRED? |
| |
| 8.PROVIDE DETAIL FOR SECURING ROOF |
| CURBS & EQUIPMENT.SHOW COMPLAINCE WITH |
| 2001 FBC 1606, FOR REQUIRED WIND LOADS. |
| |
| 9.PLANS DO NOT INDICATE CONDENSATE |
| LAYOUT, MATERIAL, AND TERMIANTION. |
| TERMINATION SHALL COMPLY WITH 2001 |
| FBC(M)307.2.1.AND FBC 1503.4.4. |
| |
| 10.PROVIDE ADDTIONAL INFORMATION FOR |
| THE GENERATOR ON PLAN SHEET P-2. |
| PROVIDE MANUFACTURER'S SUBMITTAL DATA. |
| |
| 11.PLEASE INDCIATE ALL APPLIANCES THAT |
| WILL UTILIZE THE GAS.PLEASE INDICATE |
| NATURAL OR LP GAS. |
| |