2005-06-23 00:00:00DENIED:
 1.PLAN SHEET AC-1 DUCT PENTRATING WALL
 BETWEEN THE STORAGE ROOM AND CLASS ROOM
 #6 INDICATES A FIRE DAMPER.ACCORDING
 TO PLAN SHEET A-2 THE FIRE DAMPER SHOULD
 BE LOCATED BETWEEN THE CORRIDOR AND THE
 STORAGE ROOM, PLEASE CLARIFY.
  
 2.PROVIDE CURB DETAIL & TERMINATION
 LOCATION FOR EXHAUST FANS.PROVIDE
 DISTANCE FROM FRESH AIR INTAKES ON THE
 RTU'S.
  
 3.PROVIDE INFORMATION FOR EXHAUST DUCT
 TO THE DRYER LOCATED IN THE "HOUSEHOLD
 ROOM".INDICATE DUCT SIZE, MATERIAL,
 AND TERMINATION.PLEASE NOTE, PER 2001
 FBC(M) 504.6, MAKEUP AIR SHALL BE
 PROVIDED FOR INTALLATIONS THAT EXHAUST
 GREATER THAN 200 CFM.
  
 4.PLAN SHEET AC-1 INDICATES RETURN AIR
 IN THE LAUNDRY AREA.WILL THIS BE
 RECIRCULATED?
  
 5.PROVIDE SPECIFICATION ON THE DRYER.
  
 6.INDICATE WHAT KIND OF FOOD PREP WILL
 BE TAKING PLACE.PLAN SHEET A-2
 INDICATES HOT & COLD FOOD.PLEASE
 INDICATE ANY "COOKING" EQUIPMENT OR
 APPLIANCES.
  
 7.PLAN SHEET AC-1 INDICATES
 DISHWASHER, PLEASE PROVIDE SUBMITTAL
 DATA.WILL A HEAT HOOD BE REQUIRED?
  
 8.PROVIDE DETAIL FOR SECURING ROOF
 CURBS & EQUIPMENT.SHOW COMPLAINCE WITH
 2001 FBC 1606, FOR REQUIRED WIND LOADS.
  
 9.PLANS DO NOT INDICATE CONDENSATE
 LAYOUT, MATERIAL, AND TERMIANTION.
 TERMINATION SHALL COMPLY WITH 2001
 FBC(M)307.2.1.AND FBC 1503.4.4.
  
 10.PROVIDE ADDTIONAL INFORMATION FOR
 THE GENERATOR ON PLAN SHEET P-2.
 PROVIDE MANUFACTURER'S SUBMITTAL DATA.
  
 11.PLEASE INDCIATE ALL APPLIANCES THAT
 WILL UTILIZE THE GAS.PLEASE INDICATE
 NATURAL OR LP GAS.
  