Plan Review Notes For Permit 05050354 |
Permit Number |
05050354 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-01 00:00:00 | ****DENIED**** | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR THE FIRE SPRINKLER AND | | FIRE ALARM SYSTEMS. | | | | 2) IN ACCORDANCE WITH LOCAL | | REQUIREMENTS, MONITORING OF THE FIRE | | ALARM SYSTEM SHALL BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE. | | | | 3) PLEASE ILLUSTRATE THE OCCUPANCY | | CLASSIFICATION ON THE DRAWINGS. | | | | 4) AN ADDRESS NUMBER IS REQUIRED ON THE | | BUILDING THAT IS A MINIMUM OF 6" IN | | HEIGHT AND CONTRASTING TO THE | | BACKGROUND. | | | | 5) PLEASE SHOW THE LOCATION OF THE FIRE | | DEPARTMENT CONNECTION. | | | | 6) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATIONS FOR THE WALLS AND | | CEILINGS. | | | | 7) IF THIS IS A NEW FIRE SPRINKLER | | INSTALLATION, PLEASE PROVIDE DETAILS FOR | | THE DOUBLE CHECK DETECTOR ASSEMBLY. | | | | 8) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED TO BE MOUNTED NOT TO EXCEED 75' | | TRAVEL DISTANCE. | | | | 9) IN ACCORDANCE WITH LOCAL | | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL | | BE WIRED INTO THE FIRE ALARM SYSTEM TO | | CAUSE A GENERAL FIRE ALARM, NOT A | | SUPERVISORY SIGNAL. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2951 OR 805-6722 |
|