Plan Review Notes
Plan Review Notes For Permit 05050354
Permit Number 05050354
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-06-01 00:00:00****DENIED****
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS.
  
 2) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, MONITORING OF THE FIRE
 ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 3) PLEASE ILLUSTRATE THE OCCUPANCY
 CLASSIFICATION ON THE DRAWINGS.
  
 4) AN ADDRESS NUMBER IS REQUIRED ON THE
 BUILDING THAT IS A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 5) PLEASE SHOW THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION.
  
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS FOR THE WALLS AND
 CEILINGS.
  
 7) IF THIS IS A NEW FIRE SPRINKLER
 INSTALLATION, PLEASE PROVIDE DETAILS FOR
 THE DOUBLE CHECK DETECTOR ASSEMBLY.
  
 8) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 9) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 BE WIRED INTO THE FIRE ALARM SYSTEM TO
 CAUSE A GENERAL FIRE ALARM, NOT A
 SUPERVISORY SIGNAL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722