Plan Review Notes
Plan Review Notes For Permit 05050247
Permit Number 05050247
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE ALL FROM THE
 PREVIOUS REVIEW.
  
 1.)PROVIDE A COPY OF THE IMPACT FEE
 RECEIPT.
  
 2.)WINDOW C DOES NOT MEET EMERGENCY
 EGRESS REQUIREMENTS FBC1005.2.THE
 ARCHITECT HAS ADDED A NOTE "ADJUST
 SIZE".IT IS NOT ACCEPTABLE TO SPECIFY
 A WINDOW WHICH IS CLEARLY NOT CODE
 COMPLIANT AND ASK FOR THE CONTRACTOR TO
 ADJUST THE SIZE IN THE FIELD.THE PLANS
 ARE TO BE CODE COMPLIANT, AND THIS IS
 CONSIDERED A LIFE SAFETY ISSUE.PLEASE
 SPECIFY A COMPLIANT WINDOW.FEEL FREE
 TO CONTACT ME IF YOU NEED ASSISTANCE.
  
 3.)ADDITIONAL FEES DUE, SEE ATTACHED.
  
 4.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 5.)PLEASE PROVIDE PRODUCT APPROVALS
 FOR THE FOLLOWING:
  
 FRONT DOOR (IMPACT GLASS)
 SLIDIING GLASS DOOR
 LOUVERS
 ROOF (ILLEGIBLE)
  
 ANY PRODUCT APPROVALS NOT SUBMITTED
 CORRECTLY PRIOR TO PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS.
  
 6.)SEE ATTACHED FS553.80(2)(B).
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.