 PROVISO
  
 PLEASE MAKE THESE CHANGES AND RESUBMIT
 FOR REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} PROVIDE OUTSIDE RECEPTACLES PER
 210.52(E).
  
 2} RECEPTACLES MUST BE ADDED IN THE
 KITCHEN PER 210.52(C)(1) SPACING.
  
 3} SEE RECEPTACLE SPACING, BED #1 AND
 MASTER TO COMPLY WITH 210.52(A)(1)&(2).
  
 4} THE DINING ROOM MUST BE ON A SMALL
 APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 NOTE: THE PANEL IN THE LAUNDRY LOCATED
 BETWEEN THE SINK ABD THE WASHING MACHINE
 WOULD BE BETTER PLACED FOR FUTURE
 MAINTENANCE IF IT WERE ON THE OPPOSITE
 WALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  