Plan Review Notes For Permit 05050243 |
Permit Number |
05050243 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-20 00:00:00 | | | PROVISO | | | | PLEASE MAKE THESE CHANGES AND RESUBMIT | | FOR REVIEW PRIOR TO ROUGH INSPECTION. | | | | 1} PROVIDE OUTSIDE RECEPTACLES PER | | 210.52(E). | | | | 2} RECEPTACLES MUST BE ADDED IN THE | | KITCHEN PER 210.52(C)(1) SPACING. | | | | 3} SEE RECEPTACLE SPACING, BED #1 AND | | MASTER TO COMPLY WITH 210.52(A)(1)&(2). | | | | 4} THE DINING ROOM MUST BE ON A SMALL | | APPLIANCE CIRCUIT PER 210.52(B)(1). | | | | NOTE: THE PANEL IN THE LAUNDRY LOCATED | | BETWEEN THE SINK ABD THE WASHING MACHINE | | WOULD BE BETTER PLACED FOR FUTURE | | MAINTENANCE IF IT WERE ON THE OPPOSITE | | WALL. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|