Plan Review Notes For Permit 05050243 |
Permit Number |
05050243 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-11 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.)THERE IS A HOLD ON THIS PROPERTY, | | SEE ATTACHED.PLEASE ADDRESS. | | | | 2.)SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC FBC13-101.2. | | | | 3.)WINDOW B IS REQUIRED TO BE SAFETY | | GLASS FBC2405.1. | | | | 4.)WINDOW C DOES NOT MEET EMERGENCY | | EGRESS REQUIREMENTS (SINGLE HUNG 48? | | HIGH), FBC1005.2. | | | | 5.)ADDITIONAL FEES DUE, SEE ATTACHED | | (VALUE ADJUSTMENT). | | | | 6.)A MEANS OF ESCAPE IS TO BE | | PROVIDED, FBC1005.4.5.THE FRONT DOOR | | IS SHOWN AS A WOOD DOOR (NO GLAZING) BUT | | THE PRODUCT APPROVALS SUBMITTED WERE FOR | | GLAZED STEEL DOORS. | | | | 7.)PROVIDE A HURRICANE SHUTTER | | INSTALLATION SCHEDULE, SEE ATTACHED. | | | | 8.)PROVIDE PRODUCT APPROVALS FOR: | | | | LOUVERS | | ALUMINUM SIDING | | ROOF (ILLEGIBLE) | | FRONT DOOR | | | | ANY PRODUCT APPROVALS NOT SUBMITTED | | PRIOR TO ISSUANCE WILL REQUIRE SEPARATE | | PERMITS FOR THOSE ITEMS. | | | | 9.)PROVIDE A DETAIL FOR THE GUARDRAIL | | IN COMPLIANCE WITH FBC1015 (SHOW PICKET | | SPACING). |
|