Plan Review Notes
Plan Review Notes For Permit 05050210
Permit Number 05050210
Review Stop P
Sequence Number 2
Notes
Date Text
2005-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1. THE FOLLOWING SHEETS HAVE NOT BEEN
 SEALED AS REQUIRED BY SECTION 104.2.2
 AND FLORIDA STATUTES:
 CV, GN-1, A-2.01, AND A-4.01
 2. THE SIGNATURES OF THE NEW SHEETS DO
 NOT MATCH THE SIGNATURES OF THE SHEET
 SUBMITTED PREVIOUSLY. PLEASE SUBMIT A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE OF THE
 ARCHITECT OF RECORD FOR OUR FILES. THE
 LETTER SHALL HAVE A TITLE BLOCK AS
 REQUIRED BY FAC 61G1-16.004
 3. FROM PREVIOUS REVIEW:
 4. SHT P2.1 DOMESTIC WATER RISER. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. A
 WATER HAMMER ARRESTOR IS REQUIRED ON THE
 LINE TO THE DISH WASHER AND TO THE ICE
 MAKER IF SUPPLIED. SECTION 604.9.
 RESPONSE NOTED, BUT THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE AND IF THE MANUF. REQUIRES
 ACCESS, AN ACCESS PANEL IS REQUIRED OR
 THE ARRESTOR CAN BE LOCATED UNDERNEATH
 THE SINK FOR ACCESS. SUBMIT MANUFACTURE
 INFORMATION ON THE TYPE AND MODEL OF THE
 WATER HAMMER ARRESTOR TO BE USED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]