Plan Review Notes
Plan Review Notes For Permit 05050210
Permit Number 05050210
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-05 00:00:00*** UNSAT ****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 1)NOTE: PLEASE SEE RESPONSE LTR MENTIONS
 SIZING OF GUTTER PROVIDED, HOWEVER
 PLEASE SEE ONLY 12X12 IS SHOWN , NO
 LENGTH WAS PORVIDED.?
 366,
  
 2)NOTE: PLEASE SUBMIT MANUFACTURE
 SPEC/CUT SHEETS FOR MTS.
 PLEASE SEE RESPONSE LTR MENTIONS A "MAIN
 BRKR ON GEN WILL BE THE DISCONNECTING
 MEANS AS PERMITTED IN 225.3.4B" PLEASE
 SEE 225.3.4B, THIS CODE DOES NOT SEEM TO
 APPLY.
 THE MTS WILL BE CONSIDERED THE DISC
 MEANS. THE BRKR ON A GEN IS NOT
 ACCEPTABLEAS THE MEANS OF DISC.
 PLEASE SEE 225.31-225.36.,110.27 ETC.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY REPLACE WITH NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  