1 |
|
Notes |
Date |
Text |
2005-06-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | 1. SHTS A-2.01 & A-2.3 PER SECTION | | 11-4.24.5 THE CLEAR FLOOR SPACE SHALL BE | | PROVIDED IN FRONT OF THE SINK TO ALLOW | | FORWARD APPROACH. THE CLEAR FLOOR SPACE | | SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH | | THE SINK. THE CABINET SHALL NOT HAVE | | DOORS IN THE CLEAR FLOOR SPACE. | | 2. SHT P0.1 WATER HEATER DETAIL. THERMAL | | EXPANSION CONTROL REQUIRED PER SECTION | | 607.3.2. | | 3. SHTS P0.1 & P2.1 DEMOLITION, IN THE | | INSTALLATION OR REMOVAL OF ANY PART OF | | THE DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | PROHIBITED. CLEANOUTS AND/OR FUTURE | | FIXTURES SHALL NOT BE CONSIDERED AS DEAD | | ENDS. SECTION 704.5. | | 4. SHT P2.1 DOMESTIC WATER RISER. WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | IN THE CEILING AS SHOWN. PDI-WH 201. - | | WATER HAMMER ARRESTOR IS REQUIRED ON THE | | LINE TO THE DISH WASHER AND TO THE ICE | | MAKER IF SUPPLIED. SECTION 604.9. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|