2005-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHTS A-2.01 & A-2.3 PER SECTION
 11-4.24.5 THE CLEAR FLOOR SPACE SHALL BE
 PROVIDED IN FRONT OF THE SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. THE CABINET SHALL NOT HAVE
 DOORS IN THE CLEAR FLOOR SPACE.
 2. SHT P0.1 WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL REQUIRED PER SECTION
 607.3.2.
 3. SHTS P0.1 & P2.1 DEMOLITION, IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF
 THE DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. CLEANOUTS AND/OR FUTURE
 FIXTURES SHALL NOT BE CONSIDERED AS DEAD
 ENDS. SECTION 704.5.
 4. SHT P2.1 DOMESTIC WATER RISER. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. -
 WATER HAMMER ARRESTOR IS REQUIRED ON THE
 LINE TO THE DISH WASHER AND TO THE ICE
 MAKER IF SUPPLIED. SECTION 604.9.
  
 REVIEW BY KEN STEVENS