Plan Review Notes
Plan Review Notes For Permit 05050210
Permit Number 05050210
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-18 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS FOR PANELS ARE SHOWN,
 HOWEVER PLEASE INDICATE FOR MAIN AND
 MTS.
  
 2)NOTE: PLEASE SHOW SIZE OF GUTTER TO BE
 INSTALLED PER 366 OF THE NEC.
 PLEASE SEE PLANS SHALL NOT CONTAIN
 REFERENCE TO CODES IN WHOLE OR IN PART
 FBC 104.2.1
  
 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 ATTACHMENT PER 250.50.
 PLEASE ALSO SEE THE CODE SHALL NOT BE
 REFERENCED IN WHOLE OR IN PART.
 FBC 104.2.1
  
 4)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING CONDUCTORS SHALL BE
 INSTALLED FROM METER TI THE FIRST MEANS
 OF DISCONNECT. PLEASE SEE RISE INDICATES
 AND EQUIP. GRND.
  
 5)NOTE: PLEASE SEE RISER INDICATES
 "GENERATORS CABLES" FOR PORTABLE GEN.
 UNIT. PLEASE CLARIFY THESE CABLES AS
 SHOWN. WILL THEY BE CONNECTED INTO ATS?
 WILL THEY TERMINATE INTO AN ENCLOSURE
 OUTSIDE? ETC. OR WILL THESE CABLES BE
 INSTALLED IN FUTURE? IF SO PLEASE ADD
 NOTE THAT CABLES BE FUTURE AND NOT
 INSTALLED AT THIS TIME.
  
 6)NOTE: PLEASE SUBMIT MANUFACTURE SPECS
 FOR MTS.
 PLEASE SEE MTS SHALL HAVE A MANUAL MEANS
 OF DISCONNECT LOCATED ON THE OUTSIDE OF
 THE MTS.
  
 7)NOTE: PLEASE VERIFY BOTH PANELS A AND
 B SEEM TO INDICATE MCB'S . THIS IS ONLY
 A NOTE. IFMLO, PLEASE ADJUST PANEL
 INFORMATION.
  
 8)NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED. ONLY CONNNECTED LOADS
 SHOWN.
 PLEASE INCLUDE/SHOW ALL CONTINUOUS LOADS
 AND LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
  
 9)NOTE: PLEASE SEE 225.31-225.36 FOR
 FEEDERS FROM GEN.
 PLEASE SEE GROUPING OF MAINS REQUIRED.
  
 10)NOTE: PLEASE VERIFY REQUIRED SIGN
 CIRCUIT PER 600.5
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETSAND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  