2005-05-06 00:00:00BUILDING PLAN REVIEW
 PERMIT:05050056
 ADD: 3901 S FLAGLER
 CONT: DBK INDUSTRIES
 TEL: (954)581-1994
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ARCHITECTURAL PLAN IS A COPY NOT AN
 ORIGINAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
  
 FL STATE STAT: 61G15-23.002 ENGINEERS
 TO PROVIDE HEADER STRIP(TITLE BLOCK)
 WITH NAME, ADDRESS &LICENSE NUMBER
  
 FL ATATE STAT: 61G16.003 ARCHITECTS
 NOT COPY (SITE PLAN), RAISED SEAL AND
 ORIGINAL SIGNATURES
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PERMIT APPLICATION INDICATES:
 1) REPLACING CARPORT ROOF WITH 5RIB
 ALUMINIUM PAN ROOF
 2) REPLACE 7 4X4 STEEL POST W/3'X3'
 CONCRETE FOOTER.
  
 LOCATION OF CANOPY IS NOT PROVIDED ON
 THE SITE PLAN?
  
 3) THE INFORMATION SUBMITTED UNDER THE
 NAME CAMERON ASHLEY IS FOR SCREEN ROOMS
 NOT FOR A CARPORT. SECONDLY NO TABLES OR
 MATERIALS WERE HIGHLIGHTED AS TO WHAT
 THE ENGINEER OF RECORD HAD APPROVED FOR
 WIND LOADS, OR GRAVITY LOADS.THIRD NO
 SHEET SHOWING J. POTTS HAS REVIEWED AND
 APPROVED THIS DESIGN.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026