Plan Review Notes For Permit 05050054 |
Permit Number |
05050054 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-24 00:00:00 | | | PLEASE SUBMIT THE MANUFACTURERS | | SPECIFICATIONS FOR THE GENERATOR AND THE | | TRANSFER SWITCH. | | | | PLEASE DRAW A SITE PLAN TO SHOW WHERE | | THE 200 AMP DISCONNECT IS LOCATED.IS IT | | ON A BUILDING OR IN THE GENERATOR? | | | | THE LINE DRAWING DOES NOT SHOW HOW | | UTILITY POWER IS TRANSFERRED. | | | | PLEASE NOTE THAT DISCONNECTS MUST BE | | GROUPED PER 225.34. | | | | SEE 225.32 FOR DISCONNECTS AT THE GARAGE | | AND HOUSE. | | | | SEE 250.30 AND 250.32D FOR GROUNDING | | REQUIREMENTS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|