Plan Review Notes For Permit 05042127 |
Permit Number |
05042127 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-03 00:00:00 | PROVISO: | | 1.TRANSFER GRILLES FROM THE BEDROOMS | | SHALL BE A MINIMUM OF 8" X 8".TRANSFER | | GRILLE FROM THE MASTER BEDROOM SHALL BE | | A MINIMUM OF 10" X 12".SIZING IS IN | | ACCORDANCE WITH 2001 FBC(M)601.4 | | EXCEPTION #2 & 3. | | | | 2.TRANSFER DUCTS SHALL COMPLY WITH | | 2001 FBC(M)601.4 EXCEPTION #1 & 3. SEE | | THE ATTACHED SCHEDULE FOR PROPER SIZING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|