Plan Review Notes
Plan Review Notes For Permit 05042127
Permit Number 05042127
Review Stop M
Sequence Number 1
Notes
Date Text
2005-05-03 00:00:00PROVISO:
 1.TRANSFER GRILLES FROM THE BEDROOMS
 SHALL BE A MINIMUM OF 8" X 8".TRANSFER
 GRILLE FROM THE MASTER BEDROOM SHALL BE
 A MINIMUM OF 10" X 12".SIZING IS IN
 ACCORDANCE WITH 2001 FBC(M)601.4
 EXCEPTION #2 & 3.
  
 2.TRANSFER DUCTS SHALL COMPLY WITH
 2001 FBC(M)601.4 EXCEPTION #1 & 3. SEE
 THE ATTACHED SCHEDULE FOR PROPER SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.