2005-09-06 00:00:00*** PROVISO ***
 RETURN AIR TRANSFER DUCTS MUST BE 1 1/2
 TIMES LARGER THAN SUPPLY AIR. PER. 2001
 FBC/M 601.4 EXECPTION: 1 .
 EX. BEDROOM 2&3 8" SUPPLY AIR DUCT,
 RETURN AIR DUCT NEEDS TO BE 10". OFFICE
 6" SUPPLY AIR DUCT, RETURN AIR DUCT
 NEEDS TO BE 10".
  
 RETURN AIR DUCTS ON 2ND. FLOOR AT 24X12
 RAG IN HALLWAY ARE DIFFICULT TO SEE ON
 PLANS (IF TRANSFER DUCTS).