Plan Review Notes For Permit 05041398 |
Permit Number |
05041398 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | FBC-2001 CHAPTER 1 | | | | A. FROM PREVIOUS REVIEW: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | 3. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | 4. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2001 FUEL GAS CODE | | SECS. 502 THRU 506. | | | | B. NO RESPONSE TO THESE COMMENTS WERE | | SUBMITTED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|