2005-05-05 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTE 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 5) A RESIDENTIAL GENERATOR PERMIT SHALL
 BE APPLIED FOR BY THE CONTRACTOR THAT
 SETS AND HOOKS UP THE GENERATOR. THE
 FOLLOWING INFORMATION IS REQUIRED:
 A. A SURVEY/SITE PLAN IS REQUIRED
 SHOWING THE LOCATION OF THE GENERATOR
 AND THE SET BACKS FOR THE PROPERTY LINE.
 THE DISTANCE FROM ALL OPENINGS IN THE
 STRUCTURE SHALL BE SHOWN ON THE PLAN.
 B. REVIEWS BY THE FOLLOWING ARE
 REQUIRED PRIOR TO ANY PERMIT BEING
 ISSUED FOR THE GENERATOR. ZONING,
 MECHANICAL, ELECTRIC, BUILDING, AND FUEL
 GAS.
 6) ALL INFORMATION, DRAWINGS,
 SPECIICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN .
 SECTION 104.2.1.
  