Plan Review Notes For Permit 05041273 |
Permit Number |
05041273 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2005-12-21 00:00:00 | **** UNSAT **** | | | | 1)NOTE: PLEASE SEE PLANS ARE NOW COMING | | ON WITH THE TRANSFORMER/DISCONNECTS | | BEING LOCATED IN WHAT APPEARS TO BE A | | FIRE RATED EXIT CORRIDOR. | | PLEASE SEE THE EXTEND OF THE BLDG | | OCCUPANCY LOAD IS KNOWN FOR EXIT | | REQUIREMENTS. | | PLEASE SEE THIS EQUIPMENT WOULD PROMOTE | | A MAJOR TRIPPING HAZARD LOCATED IN THIS | | LOCATION. | | PLEASE ALSO SEE POSSIBLE COMMENT FROM | | BLDG REVIEW, WHEREAS PLANS SEEM TO SHOW | | THE EGRESS DOOR FOR EXIT STAIR WAY | | OPENING INTO THE HALL? | | | | 2)NOTE: PLEASE KNOW, THIS TRANSFORMER | | MAY NOT BE MOUNTED ABOVE ANY | | "DROP/SUSPENDED" CEILING IN HALLWAY PER | | 450.13B | | | | ** PLEASE SEE BLDG REVIEW AND POSSIBLE | | FIRE REVIEW OF EQUIPMENT INSTALLATION | | LOCATION. | | | | ONCE ANY REVISION IS DONE AND REVIEWED | | AND STAMPED BY BLDG AND FIRE, THE | | ELECTRICAL REVISION MAY THEN BE STAMPED. | | | | IF THERE ARE ANY QUESTION, PLEASE DO NOT | | HESITATE IN CONTACITNG THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|