Plan Review Notes
Plan Review Notes For Permit 05041273
Permit Number 05041273
Review Stop E
Sequence Number 4
Notes
Date Text
2005-09-21 00:00:00*********** UNSAT 4TH REVIEW *********
  
 1)NOTE: PLEASE SEE ELECTRICAL CODE
 COMPLIANCE COMMENTS HAVE BEEN ADDRESSED
 BY NEW ENGINEER OF RECORD, HOWEVER
 PLEASE SEE COMMENT BELOW.
  
 PLEASE SEE NE PLANS BY ENGINEER DO NOT
 CONTAIN NEW LAYOUT FOR ELECTRICAL
 LIGHTING/CEILING PLANS.
 THE EXISTING LIGHTING/CEILING PLANS
 "A-3" COULD HAVE BEEN USED FOR LIGHTING
 LAYOUT ONLY , HOWEVER PLEASE SEE BOTH
 SETS CONTAIN "PHOTOCOPIES" OF SIGNED AND
 SEALED PLANS BY THE ARCHITECT???
 PLEASE SEE NEW SHEET A-1 AND A-3 WHICH
 ARE NOT SIGNED, DATED AND SEALED.
 PLEASE SEE BLDG REVIEW FOR SHEET A-1.
  
 PLEASE EITHER HAVE NEW ENGINEER OF
 RECORD REVISE NEW SHEET E-1 TO INCLUDE
 NEW ELECTRICAL LIGHTING/CEILING LAYOUT
 OR PLEASE HAVE NEW SIGNED, DATED AND
 SEALED PLANS FOR SHEET A-3.
  
 IN EITHER CASE, PLEASE REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED , CORRECTED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]