Plan Review Notes
Plan Review Notes For Permit 05041273
Permit Number 05041273
Review Stop E
Sequence Number 3
Notes
Date Text
2005-08-29 00:00:00********* UNSAT 3RDREVIEW **********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS
 AND NEW COMMENTS DUE TO COMPLETE NEW
 ELECTRICAL RISER SUBMITTED.
  
 1)NOTE: PLEASE SEE RISER NOW INDICATES
 AND NEW TRANSFOMER AND 277/480V SYSTEM
 BEING SHOWN.
 PLEASE SEE FS 471.003, WHICH REQUIRES
 NEW WORK FOR 277/480V TO BE SIGNED AND
 SEALED BY AN ENGINEER/PE.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR(S) FOR TRANSFORMER.
 250.110, SIZED PER 250.122
 PLEASE ALSO SEE 250.30, 250.66 FOR
 SIZING OF GROUNDING FOR TRANSFORMER.
  
 3)NOTE: PLEASE SEE 210.8B3, 2002 NEC
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR NOW ADDING NEW LOADS TO EXISTING
 MAIN DIST SYSTEM.
 220
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B)
 ATTACHED WITH RESPECT TO DESIGN
 PROFESSIONAL AND REPEAT COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  