2005-08-29 00:00:00 | ********* UNSAT 3RDREVIEW ********** |
| |
| PLEASE SEE NOTES FROM PREVIOUS REVIEWS |
| AND NEW COMMENTS DUE TO COMPLETE NEW |
| ELECTRICAL RISER SUBMITTED. |
| |
| 1)NOTE: PLEASE SEE RISER NOW INDICATES |
| AND NEW TRANSFOMER AND 277/480V SYSTEM |
| BEING SHOWN. |
| PLEASE SEE FS 471.003, WHICH REQUIRES |
| NEW WORK FOR 277/480V TO BE SIGNED AND |
| SEALED BY AN ENGINEER/PE. |
| |
| 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR(S) FOR TRANSFORMER. |
| 250.110, SIZED PER 250.122 |
| PLEASE ALSO SEE 250.30, 250.66 FOR |
| SIZING OF GROUNDING FOR TRANSFORMER. |
| |
| 3)NOTE: PLEASE SEE 210.8B3, 2002 NEC |
| REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| TO BE GFCI PROTECTED. THIS REQUIREMENT |
| APPLIES TO EACH AND EVERY 15- AND |
| 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| WHETHER OR NOT THE RECEPTACLE SERVES |
| COUNTERTOP APPLIANCES. |
| |
| 4)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS |
| FOR NOW ADDING NEW LOADS TO EXISTING |
| MAIN DIST SYSTEM. |
| 220 |
| |
| 5)NOTE: PLEASE SEE FS 553.80(2)(B) |
| ATTACHED WITH RESPECT TO DESIGN |
| PROFESSIONAL AND REPEAT COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |