Plan Review Notes
Plan Review Notes For Permit 05041273
Permit Number 05041273
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-15 00:00:00************ UNSAT *************
  
  
 PLEASE SEE A NEW ELECTRICAL RISER FOR
 NEW SERVICE IS NOW BEING SUBMITTED.
  
 1)NOTE: PLEASE SUBMIT/SHOW AIC RATING
 FOR NEW MAIN. IT IS NOTED THAT AIC
 RATING IS INDICATED FOR SUB PANEL.
 110.9,215.5
  
 2)NOTE: PLEASE INDICATE SIZE OF EXISTING
 METER. PREVIOUS SERVICE RISER INDICATED
 100A'S? NEW MAIN IS 200A'S.
 215.5
  
 3)NOTE: PLEASE SEE NOW AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN FROM METER
 TO MAIN/FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24, EQUIPMENT
 GROUNDING CONDUCTORS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 5)NOTE: PLEASE SEE ADDRESS ON PLANS
 INDICATE 420 HAMPTON, HOWEVER PERMIT
 APPLICATION SHOWS 424 AND OUR SYSTEM
 SHOWS 424, PLEASE CORRELATE.
  
  
 PLEASE SEE PLANS ARE COMING ABCK FOR
 PLUMBING NOTES, PLEASE MAKE THE ABOVE
 CHANGES/CORRECTIONS AT THIS TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]