2005-07-15 00:00:00 | ************ UNSAT ************* |
| |
| |
| PLEASE SEE A NEW ELECTRICAL RISER FOR |
| NEW SERVICE IS NOW BEING SUBMITTED. |
| |
| 1)NOTE: PLEASE SUBMIT/SHOW AIC RATING |
| FOR NEW MAIN. IT IS NOTED THAT AIC |
| RATING IS INDICATED FOR SUB PANEL. |
| 110.9,215.5 |
| |
| 2)NOTE: PLEASE INDICATE SIZE OF EXISTING |
| METER. PREVIOUS SERVICE RISER INDICATED |
| 100A'S? NEW MAIN IS 200A'S. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE NOW AN EQUIPMENT |
| GROUNDING CONDUCTOR IS SHOWN FROM METER |
| TO MAIN/FIRST MEANS OF DISCONNECT. |
| PLEASE SEE 250.6,250.24, EQUIPMENT |
| GROUNDING CONDUCTORS ARE ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| |
| 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| KITCHENS TO BE GFCI PROTECTED. THIS |
| REQUIREMENT APPLIES TO EACH AND EVERY |
| 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| RECEPTACLE, WHETHER OR NOT THE |
| RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| |
| 5)NOTE: PLEASE SEE ADDRESS ON PLANS |
| INDICATE 420 HAMPTON, HOWEVER PERMIT |
| APPLICATION SHOWS 424 AND OUR SYSTEM |
| SHOWS 424, PLEASE CORRELATE. |
| |
| |
| PLEASE SEE PLANS ARE COMING ABCK FOR |
| PLUMBING NOTES, PLEASE MAKE THE ABOVE |
| CHANGES/CORRECTIONS AT THIS TIME. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE COPY OF OLD/VOIDED SHEETS SHALL BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |