Plan Review Notes
Plan Review Notes For Permit 05041273
Permit Number 05041273
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SUBMIT A SANITARY RISER DIAGRAM SHOW
 ALL PIPE SIZES, VENTING, AND POINTS OF
 CONNECTION AND TERMINATION. SECTION
 104.3.1.1.
 2. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS (WHERE REQUIRED BY SECTION
 604.9).
 3. SUBMIT A DETIAL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE
 FORWARD APPROACH AND EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK.
 4. A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  