Plan Review Notes
Plan Review Notes For Permit 05041273
Permit Number 05041273
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-26 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 215.5
  
 2)NOTE: PLEASE SEE PLANS SHOW TWO
 PANELS, PLEASE VERIFY IF ANY CIRCUITING
 TO OUT OF SECOND PANEL SHOWN? IF SO,
 PLEASE SUBMIT PANEL SCHEDULE AND
 CORRELATE.
 215.5
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU. PLEASE SEE UNTI IS SHWON WITH
 10KW HEAT, 40 OCP AND #8 AWG.
 240.4,310.16 ETC.
  
 5)NOTE: PLEASE SEE SERVICE IS SHOWN AS
 EXISTING, HOWEVER SERVICE AS SHOWN DOES
 NOT MEET CODE COMPLIANCE FOR SEC'S OR
 FEEDERS.
 PLEASE SEE #4 SHOWN FOR 200A'S.
 PLEASE SEE 310.16, 240.4B
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.122,250.24 ETC.
  
 7)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE AN AND ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  