2005-04-26 00:00:00 | ************ UNSAT ************ |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE PLANS SHOW TWO |
| PANELS, PLEASE VERIFY IF ANY CIRCUITING |
| TO OUT OF SECOND PANEL SHOWN? IF SO, |
| PLEASE SUBMIT PANEL SCHEDULE AND |
| CORRELATE. |
| 215.5 |
| |
| 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 4)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| FOR AHU. PLEASE SEE UNTI IS SHWON WITH |
| 10KW HEAT, 40 OCP AND #8 AWG. |
| 240.4,310.16 ETC. |
| |
| 5)NOTE: PLEASE SEE SERVICE IS SHOWN AS |
| EXISTING, HOWEVER SERVICE AS SHOWN DOES |
| NOT MEET CODE COMPLIANCE FOR SEC'S OR |
| FEEDERS. |
| PLEASE SEE #4 SHOWN FOR 200A'S. |
| PLEASE SEE 310.16, 240.4B |
| |
| 6)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN TO PANEL. |
| 250.110,250.122,250.24 ETC. |
| |
| 7)NOTE: PLEASE SEE 700.12E FOR |
| CIRCUITING OF EM/EXT LTS. |
| |
| PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE AN |
| AFFECT ON ELECTRICAL PLANS. |
| |
| PLEASE REMOVE AN AND ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |