Plan Review Notes For Permit 05041195
Permit Number 05041195
Review Stop P
Sequence Number 3
Notes
Date Text
2005-08-03 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW:
 1. SHT P-1 ALL FIXTURES THAT HAVE BEEN
 REMOVED, MOVED, OR ADDED SHALL BE SHOWN
 ON THE RISER DIAGRAM THAT REFLECTS THE
 CHANGE. THE SINK IN THE HALLWAY NEXT TO
 THE DINING ROOM IS NOT SHOWN ON THE
 RISER DIAGRAM. - SHT A-2 INDICATES THAT
 THIS SINK HAS BEEN RELOCATED FROM THE
 MASTER BEDROOM AND SHT A-1 DOES NOT SHOW
 A SINK AS EXISTING. SHT P-1 INDICATES
 THAT THIS IS AN EXISTING SINK. PLEASE
 CORRELATE ARCHITECTURAL SHEETS AND
 PLUMBING SHEET. SECTIONS 104.2.1 AND
 104.3.1.1.
 2. ALL MEP SHEETS - ENGINEERS SHALL
 INDICATE THEIR CERTIFICATE OF
 AUTHORIZATION ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
  
 REVIEW BY KEN STEVENS